III.d … adjustment
For operating the interface sensor no Ex-relevant adjustments are required.
III.e … putting into service
Before putting into service, all devices must be checked of right installation and connection. The elec-
trical supply, as well of connected devices, must be checked.
III.f … maintenance (servicing and emergency repair)
As part of regular maintenance of the Oil/Water Separator, the interface sensor must thoroughly be
cleaned using a moist cloth. Grease-dissolving cleansing agents can be used to remove any firmly cling-
ing grease or oil residues. Sharp-edged objects are unsuitable for the purpose of cleaning since they
could damage the sensor.
In case of a defect, the interface sensor must be sent back to FAFNIR or one of its representatives.
There is compliance with the requirements for the dielectric strength between the intrinsically safe circuit
and the chassis of the interface sensor with 500 V
AC
in accordance with EN 60079-11, section 6.3.13.
IV
Equipment marking
1 Manufacturer:
FAFNIR GmbH, 22525 Hamburg
2 Type designation:
SEPARIX-C …
3 Certificate number:
TÜV 03 ATEX 2368 X
4 Ex marking:
II 1 G
Ex ia IIB T4 Ga
5 CE marking:
0044
6 Technical Data
U
i
≤
15 V
L
i
< 100 µH
I
i
≤
30 mA
C
i
< 10 nF
P
i
≤
100 mW
T
a
≤
+60 °C
V
Technical data
The safety-related values are defined with:
Input voltage
U
i
≤
15 V
Input current
I
i
≤
30 mA
Input power
P
i
≤
100 mW
The externally effective capacitance and inductance are:
Internal capacity
C
i
≤
10 nF
Internal inductance
L
i
≤
100 μH
The interface sensor may be used in the following temperature ranges:
Ambient temperature
-20 °C
≤
T
a
≤
+60 °C
Medium temperature
0 °C
≤
T
F
≤
+60 °C
General information (see also EN 60079-0, section 1):
Zone 0 exists only under atmospheric conditions:
Temperature range
-20 °C … +60 °C
Pressure range
0,8 bar … 1,1 bar
Oxidants
Air (oxygen content approx. 21 %)
The interface sensor achieves a degree of protection provided by enclosure:
Degree of protection
IP68
VI
Specific conditions for use
None.