Page 19/46
Installation
4.4
Adjustment dimension
4.4.1
Adjustment dimension X for cyl. horizontal tanks according to DIN
6608/ -16/ -17/ -24 and EN 12285
(See Tables 1, 2, 3 or 7)
For tanks, the diameters of which are not detailed in the tables, the adjustment
dimension must be selected for the next largest tank diameter.
b = distance between the tank bottom and the tank lid (hexagon nut seat)
h = max. filling height / response height (see tables 1–3, 7)
D = tank diameter
x = Overfill Prevention Sensor adjustment dimension (see tables 1–3, 7)
y = control dimension to check the position of the Overfill Prevention Sensor
x
b
h
D
y
Figure 14: Tanks in accordance with DIN 6608, 6616, 6617, 6624 and EN 12285
Pr
ob
e l
en
gt
h
y = probe length – x