7
PLUS
10
GB
SINGLE- AND THREE-PHASE FOR SLIDING GATES
AND AUTOMATIONS FITTED WITH LIMIT SWITCHES
Single- (230V) and Three-phase (400V) Motors:
-
+
T1
MOTOR RUN TIME
OPEN / CLOSE
from 5 to 128s
T2
-
+
CAPACITOR
18
16
17
COMMON
M
MOTOR
U
W
V
Flashing lamp:
19 20
230V MAX 25W
4
7
DIP-SWITCH 4 and 7:
ON: Pre-flashing
OFF: No pre-flashing
ON: Lamp is not operating during
Dwell Time. Automatic Mode.
OFF: It flashes during Dwell Time .
Automatic Mode.
230V
400V
Power supply:
Hold on switched (Deadman) control:
Open and Close operations are achieved "by holding a switch on"
(no relay self-holding is involved) therefore a phisical attendance
is required to keep the gate opening or closing until either the
button or key is released.
DIP-SWITCH 6
6
ON= Deadman Control. Dip-switch 4=OFF
and Dip-switch 3=OFF
OFF= Standard Operations
Remote Controlled Operations Excluded during Dwell Time on Automatic Mode:
3
ON= Automatic Closing
OFF= Closing by Pulse
5
ON: Step by step. Stop in between
OFF: Standard Operations
With this setting it is not possible to operate the gate by remote control during the dwell time on automatic mode.
DIP-SWITCH 2=ON, 3=ON and 5=ON
2
ON: No reversing on opening
OFF: Travel reversing on any pulsing
3
DIP-SWITCH 3
ON= Automatic Closing
OFF= No Automatic. Semi-automatic
closing by pulse
Automatic / Semiautomatic:
Automatic Operation:
any pulse opens the gate, the gate stays open as long as the Dwell time
expires as set by T2 trimmer, then it closes automatically, no pulsing is required.
Semi-automatic Operation:
any pulse opens the gate that stays open. A second pulse to Close is
required for the gate to close.
Dwell Time
from 5 to 128s
T2
-
+
Pedestrian Opening:
-
+
Trimmer T3 at minimum disactivates Pedestrian Opening
from 3 to 30s. It can be activated by any pulse (eg. by remote control) superior to 2s
How it works: Set the clock to the required time. On the pre-set time the gate is automatically opened and held open. Any further
pulsing (even by remote control) is not accepted by the system until the time pre-set by the clock has expired. On expiring and
after the pre-set dwell time the gate is closed automatically.
T3 trimmer on to zero, Dip-Switch 3=ON.
Time clock installation:
DIP-SWITCH No.3=ON Automatic Closing
3
ON= Automatic Closing
OFF= No Automatic. Semi-automatic
closing by pulse
-
+
Pedestrian Trimmer
T3
set on to zero
4
3
COMMON
COMMON
OPEN
NO
External Time Clock
FADINI
l'apricancello
T3
PEDESTRIAN TIME
from 3 to 30s
230V
±
10% 50Hz
SINGLE-PHASE
21
22
NEUTRAL
S
LIVE
23
22
R
21
22
T
R
S
LIVE
23
22
400V
±
10% 50Hz
THREE-PHASE
LIVE
NEUTRAL
DWELL TIME
from 5 to 128s
Drwg. No.
4135
ELECTRICAL POWER CONNECTIONS
OPERATING MODES