Flue calculation 

A simple way to calculate whether the exhaust 
configuration is possible in combination with your 
fireplace, use the “Faber Flue App V2”: 

 
 
 
 

This is available free of charge and can be 
downloaded via: 

 

Internet: 
Android and PC (Windows Store, (Windows 10)). 
App Store:  
iPhone, iPad and Mac. 
Google Play: 
Android smart phones and Android tablets. 

 

Alternatively, you can use the calculation sheet 
(see chapter 13). 

 

The options for flue lengths and any flue restrictors 
are defined in a restrictor table, see 11.1 till 11.2. 
Start Length (STL), Total Vertical Height (TVH) and 
Total Horizontal Length (THL) are used in the table. 

 

 

Start length (STL): 

The first part that is placed on the 
fireplace and represents a certain value 
(fig. 12.1, 12.2 and 12.3 A, N and F). You 
can find this value in the upper row of the 
restrictor table. 

 

 

Total Vertical Height (TVH): 

TVH is the height difference measured 
from the top of the appliance to the 
outlet. This can be measured or 
determined in the building plan. For 
clarification, see also the TVH indication in 
the drawings (fig. 12.1, 12.2 and 12.3). 

 

 

Total Horizontal Length (THL): 

THL is the Total Horizontal Length and 
consists of elbows and pipes entirely in 
the horizontal plane. See elbows I, K and Q 
and the elements H, J, L, M, P and R  
(fig. 12.1 and 12.2). 

 

 

Horizontal length: 

The Horizontal Length consists of the 
elements H, J, L, M, P and R (fig. 12.1 and 
12.2). 

 

 

Elbows 90° in the horizontal plane: 

Horizontal elbows are elbows entirely in 
the horizontal plane 
(fig. 12.1, 12.2 and 12.3 I, K and Q). 

 
 

 

Elbows 45° or 30° in the horizontal plane. 

Horizontal elbows are elbows entirely in 
the horizontal plane. 

 

 

Elbows 90° vertical to horizontal:  

These are 90° elbows, which proceed from 
horizontal to vertical (fig. 12.2 and 12.3 G, 
O and S). 

 

 

Elbows 45° or 30° vertical to horizontal 
plane: 

These are 30° or 45° elbows vertically 
offset less than 45° (fig. 12.1 B and D). 

 

 

Pipes at an angle of inclination: 

These are pipes vertically ascending at an 
angle of 30° or 45° (fig. 12.1 C). Fill in only 
in combination with at least two 30° or 
45° elbows in the vertical part. 

 

 

Restrictor table: 

See restrictor table for the correct vertical 
(TVH) and horizontal length (THL). 

 

In case of an “X” or if the values are outside the 
restrictor table, the combination is not permitted. 
Then adjust TVH or THL. 
If a value is indicated, check that the calculated STL 
value is not lower than indicated in the restrictor 
table. In this case STL must be adjusted. 
 
The value found indicates the width of the flue 
restrictor to be placed (“0” means no flue 
restrictor). Generally a 30mm flue restrictor is 
installed (see fig. 2.5). 

 

Summary of Contents for Relaxed L Smart

Page 1: ...Installation manual Relaxed M Smart Relaxed L Smart ENG 40010635 2010 ...

Page 2: ...Installation manual Relaxed M L Smart 1 ...

Page 3: ...Installation manual Relaxed M L Smart 2 ...

Page 4: ...Installation manual Relaxed M L Smart 3 1 1 1 2 1 3 1 4 1 5 1 6 ...

Page 5: ...Installation manual Relaxed M L Smart 4 1 7 2 0 2 1 2 2 2 3 2 4 2 5 A C B 1 2 ...

Page 6: ...Installation manual Relaxed M L Smart 5 ...

Page 7: ...se note It is advisable to always install a screen for the fireplace if children elderly or disabled people are present in the same room as the fireplace If regularly vulnerable persons can be present in the room without supervision sufficient protection must always be placed around the fireplace This appliance must be installed according with the rules in force and used only in a sufficiently spa...

Page 8: ...he flue material EN 1856 1 T600 N1 D Vm L20040 O 50 Outlets fig 1 5 The balanced flue pipe for combined air supply and discharge can use a wall terminal or a roof terminal Verify that the desired outlet meets the local regulations regarding pollution and ventilation openings Please note For proper functioning the outlet must at least be 0 5m away from Corners of the building Roof overhangs and bal...

Page 9: ...d parts from the fireplace Prepare the gas connection on the gas valve 4 5 Positioning the fireplace Take into account the installation requirements see chapter 3 Place the fireplace at the right place and level it see fig 1 1 C or 1 2 C Rough height adjustment With the adjustable legs Accurate height adjustment With the adjustable feet 4 6 Installing the flue pipes Install the flue pipes accordin...

Page 10: ...aterial on the burner at once It is possible that the burner gets clogged See the supplied decoration instruction card or chapter 18 1 or 18 2 Place part of the ash material at the burner and the cover plate Place the log set Divide the rest of the ash material at the burner and the cover plate Please note Keep the pilot flame free from ash material Start the fireplace as described in the user man...

Page 11: ...nd instructions on care and cleaning of the glass Emphasize the danger of fingerprint burns at the glass Handover to customer o installation manual o user manual o decoration instruction card o suction cups o sample Faber glass polish 9 Annual maintenance Check Check and clean if necessary the combustion chamber the burner the pilot flame the wooden logs for breakage the glass es the outlet Replac...

Page 12: ...ipes entirely in the horizontal plane See elbows I K and Q and the elements H J L M P and R fig 12 1 and 12 2 Horizontal length The Horizontal Length consists of the elements H J L M P and R fig 12 1 and 12 2 Elbows 90 in the horizontal plane Horizontal elbows are elbows entirely in the horizontal plane fig 12 1 12 2 and 12 3 I K and Q Elbows 45 or 30 in the horizontal plane Horizontal elbows are ...

Page 13: ...40 00 30 00 0 00 x x x x 12 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 13 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 14 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 15 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 16 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 17 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 18 65 00 65 00 50 00 50 00 40 00 30 00 30 00 x x x x 19 6...

Page 14: ... 60 00 50 00 50 00 40 00 30 00 x x x x 12 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 13 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 14 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 15 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 16 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 17 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 18 65 00 65 00 60 00 50 00 50 00 40 00 30 0...

Page 15: ...Installation manual Relaxed M L Smart 14 12 Examples flue materials ...

Page 16: ... 5 Flue length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part number x value result rounded value Total Length in meters x 1 90 Bend vertical to horizontal x 0 4 45 Bend vertical to horizontal x 0 2 90 Bend in horizontal direction x 1 5 45 Bend in horizont...

Page 17: ... installation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top of the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend in case of roof terminal just before the terminal 0 3 In case...

Page 18: ...class B B B Energy efficiency index EEI 85 85 85 Type heating output control room temperature no no no no yes no Glen Dimplex Benelux Saturnus 8 Heerenveen The Netherlands With mechanical control of the room temperature by thermostat Control of room temperature with open window detection no With electronic control of the room temperature With electronic control of the room temperature plus day tim...

Page 19: ...Energy efficiency index EEI 84 84 84 Type heating output control room temperature no no no no yes no Diameter outlet inlet 100 150 Technical data Type indication s Relaxed Smart L Type appliance C11 C31 C91 Gas connection 3 8 Indirect heating functionality no Category II2H3 Gas rate at full mark Power requirement for permanent pilot light if applicable Ppilot 0 15 0 15 kW Other control options One...

Page 20: ...sition outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Short...

Page 21: ...Installation manual Relaxed M L Smart 20 16 Troubleshooting guide ...

Page 22: ...Installation manual Relaxed M L Smart 21 ...

Page 23: ...Installation manual Relaxed M L Smart 22 17 Dimensional drawings 17 1 Relaxed M Smart ...

Page 24: ...Installation manual Relaxed M L Smart 23 17 2 Relaxed L Smart ...

Page 25: ...Installation manual Relaxed M L Smart 24 17 3 Remote access door A9299463 ...

Page 26: ...Installation manual Relaxed M L Smart 25 17 4 Ventilation grid article number A9296400 ...

Page 27: ...Installation manual Relaxed M L Smart 26 18 Decoration instruction card 18 1 Log set Relaxed M Smart ...

Page 28: ...Installation manual Relaxed M L Smart 27 18 2 Log set Relaxed L Smart ...

Page 29: ...Installation manual Relaxed M L Smart 28 ...

Page 30: ...www faberfires com contact faberfires com Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen ...

Reviews: