Faber MatriX 1050 Series Instruction Manual Download Page 15

I n s t a l l a t i o n   I n s t r u c t i o n s

I n s t a l l a t i o n   I n s t r u c t i o n s

1 5

4.4.1 

 Hanging on the wall (1050/650-IIL,-IIR and  

 

  1050/650-III) 

The appliance can be wall-mounted with the optional wall bracket 

(see fig. 1.8).

4.5  

Installing the flue materials

• 

When penetrating a non-combustible wall or ceiling the  

 

 

opening must be at least 5mm larger than the diameter of the  

 

discharge material. At a combustible wall or ceiling is this    

 

100mm larger than the diameter of the drainage material.

• 

Horizontal sections should be installed with a slope towards  

 

the fire (3 degrees).

• 

Build the system from the fire. If this is not possible you can  

 

make use of an extendable adapter section.

• 

For truing up the exhaust system use the 0,5m. pipe, which   

 

can be shortened and ensure that the inner pipe is always    

 

2cm longer than the outer pipe.

• 

Parts, which are shortened, must be secured with a  

 

 

self-tapping screw.

• 

Wall and roof terminals can also be cut.

• 

Do not insulate but ventilate built-in flue material (approx.    

 100cm²).

 

4.6  

Constructing the false chimney

If possible, carry out a performance test at the fire before finally 

finishing the installation.

4.6.1 

False chimney

Construct the false chimney of non-combustible material in   

 

combination with metal profiles or of masonry/concrete  

 

 

blocks. 

Be aware of ventilation grids and service door (see fig. 1.0 to  

 

1.5). Place above the ventilation grids a screen plate made of  

 

non-combustible material (see fig. 1.1, 1.3 or 1.5)

Always use a lintel or reinforcing bars while bricking the    

 

outlet. They should not be placed  directly on the fire.

Built the false chimney against the appliance (see fig. 1.0 to  

 

1.5). Keep a minimum distance of 2mm between the false    

 

chimney and the appliance, because of the extension of the  

 appliance.

4.6.2 

  Installation and finishing

For installation and finishing the following points are of interest: 

H = moldings (fig. 2.4 and 2.7)

I = distance profile (fig. 2.4)

J = upper side flange combustion chamber (fig. 2.5)

K = distance holder/glass support (fig. 2.6)

L = distance holder/glass support (fig. 2.6)

Please note:

Ensure that the fire is not load-bearing with regard to the false 

chimney breast.

4.6.3 

Method I with cover strip (fig. 2.2)

Build the false chimney breast or plateau against the moldings H 

and distance profiles I (see fig. 2.4 and 2.7).

Keep a minimum distance of 2mm between the false chimney and 

the appliance, because of the extension of the appliance. 

Take into 

account the thickness of the finish!

4.6.4 

Method II without cover strip (fig. 2.3)

Remove the distance profiles “I” (see fig. 2.4).

Make sure that the screws of the front distance profile “I” will be 

replaced, in order to ensure the air tightness of the appliance.

Build the plateau against the glass supports K and L (see fig. 2.6). 

 

Keep a minimum distance of 2mm because of the extension of the 

appliance.

For the height of the plateau see point “J” (fig. 2.5).

 

5 Removing the glass

5.1  

Removing the glass from the front

MatriX 1050-I:

• 

Remove the moldings “A” left and right (fig. 3.0).

• 

Turn the left and right side clamps “B” up (fig. 3.0).

• 

Place the suction cups on the glass and slide the upper list   

 

“C” up (fig. 3.1).

• 

See fig. 3.2, number:

 

1.  Slide the glass to the top so that the bottom will  

 

  release.

 

2.  Now, carefully slide the glass to the left.

 

3.  Get the released side towards to you and put the glass  

 

 

on a safe place.

MatriX 1050-II:

• 

Remove molding “A” left or right (fig. 3.0).

• 

Turn the left or right side clamps “B” up (fig. 3.0).

• 

Place the suction cups on the glass and slide the upper list   

 

“C” up (fig. 3.3).

• 

See fig. 3.3, number:

 

1.  Slide the glass to the top so that the bottom will  

 

  release.

 

2.  Now, carefully slide the glass to the left or to the right.

 

3.  Get the released side towards to you and put the glass  

 

 

on a safe place.

MatriX 1050-III:

• 

Place the suction cups on the glass and slide the upper list   

 

“C” up (fig. 3.3).

• 

See fig. 3.3, number:

 

1.  Slide the glass to the top so that the bottom will  

 

  release.

 

4.  Get the released side towards to you and put the glass  

 

 

on a safe place.

Summary of Contents for MatriX 1050 Series

Page 1: ...MatriX 1050 serie 40011616 1714 MatriX 1050 ENG...

Page 2: ...I n s t a l l a t i o n I n s t r u c t i o n s 2 1 0 1 2 1 1 1 3...

Page 3: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 1 4 1 5 1 6 1 7 1 8 D E...

Page 4: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 2 0 2 1 F G 1 9...

Page 5: ...I n s t a l l a t i o n I n s t r u c t i o n s 5 2 2 2 3 2 4 H H I I...

Page 6: ...I n s t a l l a t i o n I n s t r u c t i o n s 6 J L K H H 2 7 2 5 2 6...

Page 7: ...I n s t a l l a t i o n I n s t r u c t i o n s 7 2 9 2 8...

Page 8: ...I n s t a l l a t i o n I n s t r u c t i o n s 8 B B A C 3 0 3 1 1 2 3 3 1 C 2 3 4 3 3 2 3 3...

Page 9: ...I n s t a l l a t i o n I n s t r u c t i o n s 9 3 4 1 2 3 5...

Page 10: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 0 4 0 4 1 4 2...

Page 11: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 1 4 3 4 4 4 5...

Page 12: ...I n s t a l l a t i o n I n s t r u c t i o n s 1 2 4 6...

Page 13: ...rials and carpeted floors etc are attracted These parts can settle as soot on cold surfaces Therefore do not light the fire shortly after installation Light the fire for the first time and run for sev...

Page 14: ...mney must be in good condition no leakage well cleaned For more information about connections to existing chimneys ask the installation manual chimney connection set 4 Preparation and installation ins...

Page 15: ...stance profile fig 2 4 J upper side flange combustion chamber fig 2 5 K distance holder glass support fig 2 6 L distance holder glass support fig 2 6 Please note Ensure that the fire is not load beari...

Page 16: ...nd pipes for gas leakage 7 3 Checking the burner pressure and primary pressure Check that the burner pressure and primary pressure match with the information listed in the manual Chapter 14 Technical...

Page 17: ...table we work with start length STL total vertical height TVH and total horizontal length THL Start length STL This is the first part that is placed on the fire and represents a certain value fig 12...

Page 18: ...2 0 2 x x x x x x x x 11 60 2 30 2 0 2 x x x x x x x x 12 60 2 30 2 0 2 x x x x x x x x 13 70 2 30 2 0 2 x x x x x x x x 14 70 2 30 2 30 2 0 2 x x x x x x x 15 70 2 30 2 30 2 0 2 x x x x x x x 16 70 2...

Page 19: ...40 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4...

Page 20: ...0 4 x x 10 50 4 50 3 50 4 50 4 50 4 45 4 45 4 x x 11 60 4 60 3 60 4 50 4 50 4 50 4 45 4 x x 12 60 4 60 3 60 4 60 4 50 4 50 4 50 4 x x 13 60 4 60 3 60 4 60 4 60 4 50 4 50 4 x x 14 70 4 70 3 60 4 60 4 6...

Page 21: ...4 60 4 60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4...

Page 22: ...60 4 60 4 60 4 60 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 60 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 70 4 70 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 70 4 70 4 70 4 70 4 70 4 70 4...

Page 23: ...I n s t a l l a t i o n I n s t r u c t i o n s 12 Examples flue materials fig 12 1 fig 12 2 fig 12 3 2 3...

Page 24: ...ntal direction x 1 5 45 Bend in horizontal direction x 1 flue pipes at an angle in meters x 0 7 meter Value Starter length STL First part on top of the appliance Flue length from 0 1m till 0 45m Flue...

Page 25: ...er just before the terminal Wall terminal 130 200 0 4 Restrictor size Value for the comma Extra information Value behind the comma Search in the table at TVH and THL and enter the value that is found...

Page 26: ...r h 720 710 Burner pressure at full mark mbar 10 5 21 28 4 Injector main burner mm 4x 1 3 1x 1 6 1x 0 8 4x 0 9 1x 0 8 4x 0 9 Reduced input restraint mm adjustable adjustable adjustable Pilot flame SIT...

Page 27: ...13 mbar gr h 860 830 Burner pressure at full mark mbar 13 8 20 5 27 1 Injector main burner mm 4x 1 3 1x 1 6 5x 0 9 5x 0 9 Reduced input restraint mm 2 1 1 6 1 6 Pilot flame SIT145 SIT145 SIT145 Code p...

Page 28: ...ets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Short roof terminal Only...

Page 29: ...t of a small piece from the sparking plug Tie wraps removed Cable is free from any metal parts 4x 1 5V AA Alkaline Thermocouple circuit is interrupted check 8 wire cable from receiver to the gas valve...

Page 30: ...ot burner is leaking Gasket between burner unit is leaking Glass seal is leaking Flue parts aren t 100 connected check flue system Replace batteries in the receiver Check the distance from thermocoupl...

Page 31: ...ulty parts RESET the receiver Gas vlave broken poor or loose contact Short circuit in wiring Install a ground cable from the gas valve to the appliance Optional Step burner function can be turned ON a...

Page 32: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 2 17 Dimensional drawings 17 1 MatriX 1050 500 I...

Page 33: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 3 17 2 MatriX 1050 500 IIL...

Page 34: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 4 17 3 MatriX 1050 500 IIR...

Page 35: ...I n s t a l l a t i o n I n s t r u c t i o n s 3 5 17 4 MatriX 1050 500 III...

Page 36: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 5 MatriX 1050 650 I 3 6...

Page 37: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 6 MatriX 1050 650 IIL 3 7...

Page 38: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 7 MatriX 1050 650 IIR 3 8...

Page 39: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 8 MatriX 1050 650 III 3 9...

Page 40: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 9 Wall bracket 1050 500 4 0...

Page 41: ...I n s t a l l a t i o n I n s t r u c t i o n s 17 9 Wall bracket 1050 650 4 1...

Page 42: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 2 17 10 Remote acces door...

Page 43: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 3 17 11 Ventilation grid...

Page 44: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 4 17 12 Adjustable feet...

Page 45: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 5...

Page 46: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 6...

Page 47: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 7...

Page 48: ...I n s t a l l a t i o n I n s t r u c t i o n s 4 8 www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen Dealerinfo...

Reviews: