Installation manual Triple M,L Smart

 

18 < 

<

 

<

 

13

 

Calculation sheet 

 

Starter length (STL) 

First part on top of the appliance 

Value 

Value 

Flue length from 0,1m till 0,45m 

0,2 

Flue length from 0,5m till 0,90m 

0,5 

Flue length from 1m till 1,4m 

Flue length from 1,5m till 2m 

1,5 

Flue length 2m or more 

Bend 90° 

0,1 

Bend 45°, 30° or 15° 

0,2 

Roof terminal 

Wall terminal 

     

…………………….. 

Total Vertical Height (TVH)  

measured height 

rounded value 

……………………………………………………   meter 

…………….   meter 

Total Horizontal Length (THL) 

Calculation 

  

Part 

number 

value 

result 

rounded value 

Total Length in meters 

……… 

…………….. 

90° Bend, vertical to 

horizontal 

……… 

0,4 

…………….. 

45° Bend, vertical to 

horizontal 

……… 

0,2 

…………….. 

90° Bend in horizontal 

direction 

……… 

1,5 

…………….. 

45° Bend in horizontal 

direction 

……… 

…………….. 

flue pipes at an angle in 

meters 

……… 

0,7 

…………….. 

Total 

……………+ 

………………….. meter 

 

 

Summary of Contents for Concept III

Page 1: ...Installation manual Triple M Smart Triple L Smart ENG 40011605 2003 ...

Page 2: ...Installation manual Triple M L Smart 1 ...

Page 3: ...Installation manual Triple M L Smart 2 ...

Page 4: ...Installation manual Triple M L Smart 3 1 0 1 1 1 2 1 3a 1 3b ...

Page 5: ...Installation manual Triple M L Smart 4 1 4 1 5 1 6 1 7 1 8 Y X ...

Page 6: ...Installation manual Triple M L Smart 5 2 0a 2 0b 2 0c 2 1 3 0 3 1 3 2 4 0 A B A Q R S T E E B ...

Page 7: ...Installation manual Triple M L Smart 6 4 1 4 2 4 3 4 4 ...

Page 8: ...Installation manual Triple M L Smart 7 ...

Page 9: ... note It is advisable to always install a screen for the fireplace if children elderly or disabled people are present in the same room as the fireplace If regularly vulnerable persons can be present in the room without supervision sufficient protection must always be placed around the fireplace This appliance must be installed according with the rules in force and used only in a sufficiently space...

Page 10: ...rify that the desired outlet meets the local regulations regarding pollution and ventilation openings Please note For proper functioning the outlet must at least be 0 5m away from Corners of the building Roof overhangs and balconies Roof edges with the exception of the ridge edge see chapter 15 C11 outlet via facade Through a wall or façade use a Faber wall outlet Depending on the flue calculation...

Page 11: ...attachment 17 5 or 17 6 4 6 Installing the flue pipes Install the flue pipes according to the installation manual supplied with the appliance 40011968 The distance to combustible materials must be min 50mm calculated from the outside of the flue pipe Never start immediately with length adjustable concentric flue pipe on the appliance Horizontal sections should be installed to allow a slope towards...

Page 12: ...d be 4mm higher as point E see fig 2 1 Perform the steps of Method II Placing the cover strips insert strip Place the horizontal cover strip Q fig 3 0 or the horizontal insert strip R fig 3 1 Place the vertical cover strips S fig 3 2 these are held in place by adjustable magnets The insert strip R can be removed by the supplied magnet T see fig 3 1 5 Removing glass 5 1 Front glass Remove the horiz...

Page 13: ...ure Turn measuring nipple B see fig 1 1 some turns open and connect a measuring hose to the gas valve The pressure must correspond to the value indicated in the technical specifications of this manual In case of deviation contact the manufacturer Please note Close both pressure measuring nipples and check for gas leakage Check ignition and burner Ignite the fireplace by using the remote control as...

Page 14: ...ribed in chapter 7 For an extensive maintenance instruction maintenance protocol gas fires see 10 Conversion to other gas type This can only be done by replacing the burner To do so please contact your dealer Always provide the type and serial number of the appliance when ordering 11 Flue calculation A simple way to calculate whether the exhaust configuration is possible in combination with your f...

Page 15: ... vertical fig 12 2 and 12 3 G O and S Elbows 45 or 30 vertical to horizontal plane These are 30 or 45 elbows vertically offset less than 45 fig 12 1 B and D Pipes at an angle of inclination These are pipes vertically ascending at an angle of 30 or 45 fig 12 1 C Fill in only in combination with at least two 30 or 45 elbows in the vertical part Restrictor table See restrictor table for the correct v...

Page 16: ...00 50 00 40 00 40 00 30 00 x x x x 12 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 13 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 14 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 15 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 16 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 17 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 18 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x ...

Page 17: ...00 50 00 40 00 30 00 x x x x 12 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 13 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 14 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 15 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 16 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 17 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x 18 65 00 65 00 60 00 50 00 50 00 40 00 30 00 x x x x ...

Page 18: ...Installation manual Triple M L Smart 17 12 Examples flue materials ...

Page 19: ...5 Flue length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part number x value result rounded value Total Length in meters x 1 90 Bend vertical to horizontal x 0 4 45 Bend vertical to horizontal x 0 2 90 Bend in horizontal direction x 1 5 45 Bend in horizonta...

Page 20: ...installation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top of the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend in case of roof terminal just before the terminal 0 3 In case ...

Page 21: ...ergy efficiency index EEI 87 87 87 Type heating output control room temperature no no no no yes no Glen Dimplex Benelux Saturnus 8 Heerenveen The Netherlands With mechanical control of the room temperature by thermostat Control of room temperature with open window detection no With electronic control of the room temperature With electronic control of the room temperature plus day time switch With ...

Page 22: ... B Energy efficiency index EEI 86 86 86 Type heating output control room temperature no no no no yes no Diameter outlet inlet 100 150 Technical data Type indication s Triple Smart L Type appliance C11 C31 C91 Gas connection 3 8 Indirect heating functionality no Category II2H3 Gas rate at full mark Power requirement for permanent pilot light if applicable Ppilot 0 15 0 15 kW Other control options O...

Page 23: ...ition outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Short ...

Page 24: ...Installation manual Triple M L Smart 23 16 Troubleshooting guide ...

Page 25: ...Installation manual Triple M L Smart 24 ...

Page 26: ...Installation manual Triple M L Smart 25 17 Dimensional drawings 17 1 Triple M Smart with cover strip ...

Page 27: ...Installation manual Triple M L Smart 26 17 2 Triple M Smart with insert strip ...

Page 28: ...Installation manual Triple M L Smart 27 17 3 Triple L Smart with cover strip ...

Page 29: ...Installation manual Triple M L Smart 28 17 4 Triple L Smart with insert strip m L ...

Page 30: ...Installation manual Triple M L Smart 29 17 5 Wall bracket Triple M Smart article number A9322596 ...

Page 31: ...Installation manual Triple M L Smart 30 17 6 Wall bracket Triple L Smart article number A9322696 ...

Page 32: ...Installation manual Triple M L Smart 31 17 7 Remote access door article number A9299463 ...

Page 33: ...Installation manual Triple M L Smart 32 17 8 Ventilation grid article number A9296400 ...

Page 34: ...Installation manual Triple M L Smart 33 17 9 Adjustable feet article number A9319696 ...

Page 35: ...Installation manual Triple M L Smart 34 18 Decoration instruction card 18 1 Log set Triple M Smart ...

Page 36: ...Installation manual Triple M L Smart 35 18 2 Log set Triple L Smart ...

Page 37: ...Installation manual Triple M L Smart 36 ...

Page 38: ...Installation manual Triple M L Smart 37 ...

Page 39: ...Installation manual Triple M L Smart 38 ...

Page 40: ...www faberfires com contact faberfires com Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen ...

Reviews: