Measuring the reference pressure:
1.
Turn off the gas valve on the appliance;
2.
Turn the Inlet pressure test point C (see fig. 22) some and apply the
(meetslang);
3.
Check if the measured pressure is the same as the prescribed pressure;
4.
Perform this measuring when the appliance burns on full capacity and
when only the pilot ignition burns;
5.
When the pressure is too low, check if the gas pipes are made of
material wit the right diameter;
6.
When the pressure is too high (more than 5 mBar) you can’t install the
appliance and you should contact your gas company;
7.
Always check the burner pressure when the functional pressure is
right.You can measure the burner pressure by using sensor D.The
pressure should match the prescribed pressure. If this is not the case,
then contactn the supplier.
Note:
After checking the burner pressure, the Inlet pressure test point has
to be shut and checked for gas-tightness.