These self-excited and self-regulating generators, although overall dimensions  have been reduced to a minimum, 

are designed for high-level electrical performance and the maximum in operating reliability. 

 

PRELIMINARY CHECKS:

 

Before touching the machines, perform a thorough and in depth visual 

inspection, checking that components are correctly connected  up and 

that no cables or terminals are broken or loose. 

 

 

STARTING UP:

  

Make sure, when starting up, that cooling air intake and discharge openings 

are free and unblocked.  We also recommend (when the machine operates 

in a dusty environment) do periodic checks to make sure it is properly 

ventilated 

 

THE IMPORTANCE OF SPEED:

  

Frequency and voltage depend directly on rotation speed. This must be 

kept as constantly as possible on its nominal value no matter what the 

load. Drive motor speed control systems generally have a small drop in 

speed between no load and loaded conditions. We therefore 

recommend setting no load speed 3÷4% above nominal speed. 

 

CHECKING VOLTAGE:

  

All the machines are regulated during factory testing. If voltage 

readings differ from the value indicated on the name plate, this maybe 

caused by a mistaken reading or by a different rotation speed and we 

recommend regulating motor speed in order to have nominal RPM 

under loaded conditions. 

 

CHECKING THE DIODES:  

For the ohmmeter test it is best to disconnect the diode from its circuit. 

Measure continuity in one direction only. The test can also be made 

without disconnecting the diode form the circuit, using a 12V battery 

and a 45 watt light bulb (automobile light) as shown in the illustration. 

The light should turn totally on only in one direction, as shown below. 

 

 

 

WINDING RESISTANCE AT 20° C 

ROOM TEMPERATURE  

 

 

Size 

Stator 

 

Rotor 

 

Exciter 

 

  3.5 

0.7 

9.22 

5.85   

  4.0 

0.7 

9.22 

5.85 

  5.0 

0.34 

11.89 

3.46   

 

 

 

  6.0 

0.34 

11.89 

3.46 

  8.0 

0.36 

3.10 

1.43 

 10.0 

0.161 

4.03 

1.90 

 

 

 

 

 

 

 

 

Summary of Contents for HYDRO 350X-50HZ

Page 1: ...er Instruction Manual for Model HYDRO 350X 50HZ 2 WIRE Hydraulic Generator Manufacturing of Vehicle Mounted Generators Hydraulic Generators P O Box 582 Chester NY 10918 845 469 9151 Fax 845 469 7871 W...

Page 2: ...120 240 MOTOR STARTING 300 SURGE VOLTAGE REGULATOR INHERENT OUTPUT 3500 WATTS CONTINUOUS AT 100 F OIL TEMPERATURE HYDRAULIC MOTOR GEAR TYPE WITH BUILT IN FLOW CONTROL FLOW CONTROL PRESSURE COMPENSATIO...

Page 3: ...gh back pressure can be caused by spikes sent back through the return from other equipment on a common return line Another potential problem can develop if several pieces of equipment are connected to...

Page 4: ...cal load on the generator By using this setting you will have approximately 50HZ cycles or 3000 RPM when you are running at full rated load One way this can be accomplished is by using a Photo Tachome...

Page 5: ...at the load Drive motor speed control systems generally have a small drop in speed between no load and loaded conditions We therefore recommend setting no load speed 3 4 above nominal speed CHECKING V...

Page 6: ...OV25 ERLOAD SELF RE SETTING GROUND SCREW ON GENERATOR FRAME USE GREEN WIRE FOR GROUND IF USING GFCI OUTLETS U2 V2 V1 W1 CONNECT NEUTRAL TO GROUND IF USING GFCI OUTLETS NEUTRAL WHITE 240 RED OR BLACK W...

Page 7: ...572066 Coupling 24mm 22 572067 Spider 23 572068 Coupling 24 572173 Motor w Flow Control 25 572128 Rails 26 572154 Mounts 27 572206 Flow Control Cartridge 28 572261 Stud Cover PART OPTIONAL CONTROL PA...

Page 8: ...lace LOW NO LOAD VOLTAGE 1 Speed too low 2 Faulty rotary diodes 3 Breakdown in windings 4 Capacitor with high capacity 1 Check and adjust RPM s 2 Check and replace 3 Check winding resistance as per ta...

Page 9: ...INE FILTER 8 OIL COOLER 9 HYDRAULIC FLUID RESERVOIR Some units may be equipped with integral priority flow control refer to specific model number External case drain line may be required on some units...

Page 10: ...Fabco Power Instruction Manual Page 10 BRUSHLESS GENERATOR WIRING...

Page 11: ...Fabco Power Instruction Manual Page 11 HYDRAULIC MOTOR HOSE HOOK UP Fabco Power...

Page 12: ...Fabco Power Instruction Manual Page 12...

Page 13: ...Fabco Power Instruction Manual Page 13...

Reviews: