The characteristics of the cables, to be used for connecting the
Ticket Reader, are determined to ensure that the equipment and
all the devices connected to it operate well.
Electrical preparations for the ParkLite T
icket Reader lane
1
Flame-retardant cable 2 x 1,5 mm² + earth (power supply)
2
Single-pole cable 1,5 mm² with single or double insulation of the presence loop
3
Single-pole cable 1,5 mm² with single or double insulation of the transit loop
4
Cable Belden 9841 or CEAM
Y09842 with twisted pairs and screened for transmission on
data network with RS 485 protocol.
All devices must be multidrop-connected as shown in
lay-out “Data Line Connections”
5
Shielded cable for intercom 2 x 1,5 mm² (if Legacy model). Telephone pair 0,4 mm² - 275 Ohm/Km Line (Double wire), or telephone pair 0,6 mm² 122 - Ohm/Km Line (Double wire) (if Deluxe model)
6
Flame-retardant cable 2 x 0,5 mm² (input for barrier closure safety)
7
Flame-retardant cable 3 x 0,5 mm² (open/closed barrier commands)
Power supply
Presence Loop
Presence loop
T
ransit
Loop
Transit loop
Converter
Controller PL
Personal Computer
TD Slave
TR Slave
RS 485 Data Line
Intercom control unit
Safety contact
Safety contact
Open/Closed commands
Power supply T
icket Reader
230V
ac V
AC - 50 Hz
For this reason, you must use only the conductors with the
characteristics described in the table below:
3.2 TYPE OF CABLES
Fig.
10