CONTROL UNIT E604

. DESCRIPTION

Thanks to its high powered microprocessor, this 24 Vdc control unit for automatic barriers offers a wide range of 

adjustments, including deceleration and motor control.

Thanks to its integrated encoder, the control unit constantly controls rod position and movement, intervening as 

soon as a faulty situation is detected.

The 

FAILSAFE

 function makes it possible to detect any faults in the operation of the photocells.

The main operating modes and functions are set by a dip-switch, whereas the adjustment of work and pause times 

is done by self learning during programming.

2. TECHNICAL SPECIFICATIONS

Power supply voltage

230 (+6% -10%) 50 Hz / 115 Vac 60 Hz

Supply voltage of control unit

24 Vac nominal 

a

Absorbed power

3 W

Motor nominal power 

48 W

Accessories max. load

500 mA

Flashing lamp max. load

15 W

Max. load for beam lights

15 W

Max. load for courtesy light/indicator light 

5 W

Operating ambient temperature

-20° +55°

Protective fuse

F1=8 A F2=500 mA F3=630 mA (resettable)

Function logics

Automatic - Condo - Semi-automatic

Opening / closing time

Through self-learning during programming 

Pause time

Through self-learning during programming 

Obstacle detection

Trimmer-adjustable

Selectable functions  

Type of logic - Operation of open command - No mains 

power supplied function - Beam lights flashing - Safety 

devices behaviour

Terminal board inputs

Power supply - Earth - Close - Open - Open/Close - Stop 

- Safety devices - Failsafe

Inputs with connector

Battery kit - Radio connector 

Terminal board outputs

Power supply for accessories - On beam lights - Indicator 

light - Flashlight

Board dimensions

79 x 158 mm

Characteristics of optional batteries

See kit on price list

 

a

 According to mains voltage, there may be different output values on the board power feed terminals. 

Before putting into service, always check if the output voltage on the secondary winding of the transformer 

is from 20 Vac to 26 Vac. Voltage must always be measured load free.

3. PREPARATIONS

 To ensure people’s safety, all warnings and instructions in this booklet must be carefully observed. Incorrect 

installation or incorrect use of the product could cause serious harm to people.

Make sure that an adequate differential switch is  installed upstream of the system as specified by current 

regulations.

On the main power supply, install a thermal breaker with omnipolar switching.

Make sure that an adequate earthing system is available.

To lay cables, use adequate rigid and/or flexible tubes.

Always separate the connecting cables of low voltage accessories from those supplying 230/115 Vac, using 

separate sheaths to avoid possible interference.

Summary of Contents for E604

Page 1: ...68 EEC Additional information This product underwent a test in a typical uniform configuration all products manufactured by FAAC S p A Bologna 10 10 2007 Managing Director A Bassi INDEX 1 DESCRIPTION...

Page 2: ...Selectable functions Type of logic Operation of open command No mains power supplied function Beam lights flashing Safety devices behaviour Terminal board inputs Power supply Earth Close Open Open Clo...

Page 3: ...cle detection sensitivity P1 Programming push button P2 OPEN channel memory storage push button P3 OPEN CLOSE channel memory storage push button F1 Board protection fuse DL1 CLOSE contact LED DL2 OPEN...

Page 4: ...noeuvre to signal that the beam is about to move In addition to signalling beam movement the flashing light signals by a series of flashes that the beam is being powered by the buffer battery optional...

Page 5: ...mated system in order to close left hand closure is involved vice versa if the beam has to descend on the right of the automated system in order to close right hand closure is involved Two motors cann...

Page 6: ...e board The receiver module can only be inserted in one position Orient the module correctly without forcing 8 1 Memory storage of DS radio controls A maximum of two codes can be stored One on the OPE...

Page 7: ...radio controls can be memory stored on the control unit as ever associated with the activated channel When 5 seconds have elapsed from memory storage of the last radio control the control unit automat...

Page 8: ...connector is correctly connected as described in paragraph 6 3 Restore power and repeat the procedure from point 5 When the closing mechanical stop is reached the beam begins the opening manoeuvre Whe...

Page 9: ...t and restarts after release AT CLOSING Reverses on opening No effect Stops operation and at next pulse opens Reverses motion on opening Stops operation Reverses motion on opening Stops movement and o...

Page 10: ...s No effect Disables OPEN commands OPEN IN PAUSE Reloads pause time Closes immediately Reloads pause time Re closes immediately Stops operation Disables commands and at release resets pause time Disab...