13

ENGLISH

STOP

– Common ( - )

N.C. - STOP contact: 

all devices (such as pushbuttons)

which by opening a contact stop gate movement.
To install several safety stop devices, connect the N.C.
contacts in series.

N.B.

 If the STOP devices are not connected, jumper 

STOP

and 

inputs

.

B - SINGLE LEAF OPENING (N.O.): 

all devices (e.g. pushbutton)

which, by closing a contact activates opening and/or
closing of the leaf driven by motor 1.

– Common ( - )

A - TWO-LEAF OPENING (N.O.)

: all devices (pushbuttons ,

photocells, detectors, etc.) which assures opening/closing
of both leaves by closing a contact.
To install several control devices, connect the N.O. contacts
in parallel.

FSWTX

+ –  Photocell transmitter power supply (FailSafe)
To use the Fail-Safe function, power supplies to the photocell
transmitters must be connected.

W.LIGHT

+ –

  Warning lamp power supply 24 Vdc 3 W max.

For correct operation of the system, 

do not exceed

 stated

power (see table 2).

LOCK

12 Vac electric lock power supply.

d

J4 quick connector

 for decoder SL/DS - MINIDEC SL/DS - RP

433 SL/DS cards (figs. 10-11-12-13)

e

TORQUE trimmer

: thrust adjusting trimmer (anti-crushing

safety system).

f

PAUSE trimmer

: pause time adjusting trimmer (A/S/AD

logics).
Pause time is adjustable from 0 to 240 seconds.

g

OP/CL trimmer:

 Opening/Closing time adjusting trimmer

Time is adjustable from 0 to 120 seconds.

h

LEAF DELAY trimmer:

 closing leaf delay adjusting trimmer.

Leaf delay time is adjustable from 0 to 28 seconds.

N.B.:
1)

If the opening/closing time is less than the set delay
time, the delayed leaf closes at the end of the closing
time.

2)

In one-leaf application, set the leaf delay time to
minimum

i

Programming microswitches

j

Fuse F1 5x20 5 A/250 V rapid (motor power supply)

k

Fuse F2 5x20 800 mA/250 V delayed (accessories power

supply)

l

Fuse F3 5x20 1.6 A/250 V delayed (electric power supply)

m

Fuse F4 5x20 250 mA/250 V delayed (transformer power
supply)

n

  

Bridge to enable/disable the Fail-Safe (Fig. 14).

o

  

Bridge to enable/disable the wing opening

      delay(Fig. 14).

ACCESSORY

CURRENT DRAWN

PLUS 40 SL

30 mA

PLUS 433 E

20 mA

MINIDEC SL / DS

6 mA

DECODER SL / DS

20 mA / 55 mA

RP 433 SL / DS

12 mA / 6 mA

DIGICARD

15 mA

METAL DIGIKEY

15  mA

FOTOSWITCH

90 mA

DETECTOR F4 / PS6

50 mA

PHOTOBEAM

50 mA

WARNING LIGHT

150  mA

Fig. 13

Fig. 12

MINIDEC
SL/DS

PLUS

433 E

450 MPS

DECODER
SL

Fig. 11

Fig. 10

N.B.

 Use a dedicated decoder for other accessory types.

Table 2 - Current drawn by accessories

Summary of Contents for 450 MPS Control Panel

Page 1: ...Altpapier pour la nature papier recycl 100 for nature recycled paper 100 per la natura carta riciclata 100 para la naturaleza 100 papel reciclado C ERME T A Z I E N D A C E R TIF I C A T A UNI EN ISO...

Page 2: ...shall be provided for the installation with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 13 Ensure that there is a differ...

Page 3: ...hotocells A A A B B Closingphotocells OPEN TOT OPEN IND STOP Forthesafetyandfail safedevices seethe Safetydevices section N B The capacitors are provided with the operators Fig 2 Warning the max acces...

Page 4: ...are disengaged see microswitch SW4 settings They do not engage during the opening cycle In B C and B C logics they interrupt movement during the closing cycle They do not engage during the opening cyc...

Page 5: ...X TX 14 15 24 23 16 12 13 30Vcc OP CL FSW FSWTX Fig 4 A Fig 5 A Fig 6 A Fig 7 A Fig 8 A Fig 9 A Application examples The following are the commonly used connection arrangements disable fail safe No sa...

Page 6: ...system f PAUSE trimmer pause time adjusting trimmer A S AD logics Pause time is adjustable from 0 to 240 seconds g OP CL trimmer Opening Closing time adjusting trimmer Time is adjustable from 0 to 12...

Page 7: ...djust the trimmer anticlockwise To increase torque adjust the trimmer clockwise In any event FAAC advises not to exceed a torque of 15 Kg measured on the outer edge of the leaf Toensureprecisetorquead...

Page 8: ...leaves OPEN No effect OPEN inhibited No effect OPEN inhibited Stops LOGICS EP PULSES GATE STATUS OPEN A No effect if the gate must open inhibits OPEN No effect if gate must close inhibits OPEN W L on...

Page 9: ...N A B inhibited No effect OPEN A inhibited No effect OPENING PULSE HOLD TO RUN CONTROL No effect OPEN A B inhibited Interrupts operation OPEN B inhibited Interrupts operation OPEN A B inhibited No eff...

Page 10: ...ner al d a la presente publicaci n todas las modificaciones que considere oportunas para el perfeccionamiento t cnico o para cualquier otro tipo de exigencia de car cter constructivo o comercial FAAC...

Reviews: