background image

XN3 Installation and Operating Manual         

 

 

2.3

 

List of Notes 

The notes supplied in this chapter provide information on the following. 

 

Warning! 

o

 

Possible hazard to life or health. 

 

Caution 

o

 

Possible damage to property. 

 

Important 

o

 

Possible damage to enclosure, device or associated equipment. 

 

Information 

o

 

Notes on the optimum use of the device 

 

Warning!  Installation of the XN3 must be performed in accordance with          

IEC 60079-14 and IEC 60079-25. Maintenance and inspection 
must be performed in accordance with IEC 60079-17. 

 

Avertissements! 

L’installation  de  l’iWAP  XN3  doit  être  effectuée 

conformément aux normes CEI 60079-14 et CEI 60079-

25. La maintenance et l’inspection doivent être réalisées 

conformément à la norme CEI 60079-17. 

 

Warning!  Installation  of  the  XN3  is  only  to  be  performed  by  skilled 

electricians  and  instructed  personnel  in  accordance  with 
national legislation. 

 
Warning!  The XN3 contains INTRINSICALLY SAFE circuits.  
 
Warning!  The XN3 Intrinsically Safe RF output ports are located in the 

positions shown in Section 3.3. Only antennas in accordance 
with Section 3.11 
may be connected to these ports. Refer to vi 

 
Warning!  The XN3 MUST be earthed. It must be connected to the plant 

earth system using at least one of the external bonding points, 
using a minimum 4mm

2

 conductor.  The earth cable must be 

installed in accordance with the requirements of IEC 60079-
14.  Refer to Section 3.4 for details.  The cover plate earth bond 
must not be removed. 

 

Avertissements! 

L’iWAP XN3 doit être mis à la terre. Il doit être raccordé 

au  système  de  mise  à  la  terre  de  l’installation,  en 

utilisant au moins un des points externes de liaison à la 
terre, avec un conducteur 

d’un minimum de 4 mm2. Le 

câble  de  terre  doit  être  installé  conformément  aux 
exigences de la norme CEI 60079-14. 

 

Warning!  The XN3 front cover plate earth bond must not be removed. 

 
 

Summary of Contents for iWAP XN3

Page 1: ...INSTALLATION AND OPERATING MANUAL...

Page 2: ...3 and X124186 The Photograph on the front page shows the XN3 Aluminium Enclosure version For warranty information refer to Terms and Conditions at http www extronics com 2021 Extronics Limited This do...

Page 3: ...Connector 16 3 7 Fuse Rating 16 3 8 External Overcurrent Protection 16 3 9 Data Connections 17 3 9 1 Copper Ethernet 17 3 9 2 Power Over Ethernet POE 17 3 9 3 Optical Fibre 17 3 9 4 Console Port 18 3...

Page 4: ...NT2xx range of high quality rugged outdoor antennas Any antennas not listed in the Extronics range must be assessed by the user to ensure they meet the requirements for installation of non electrical...

Page 5: ...losure shall only be with a damp cloth L quipement ne doit pas tre mont dans une zone l atmosph re haut d bit d air charg de poussi re En outre le nettoyage du bo tier ne doit tre effectu qu avec un c...

Page 6: ...nstructed personnel in accordance with national legislation Warning The XN3 contains INTRINSICALLY SAFE circuits Warning The XN3 Intrinsically Safe RF output ports are located in the positions shown i...

Page 7: ...N3 enclosure must be secured only with the bolts supplied and these must be tightened to the correct torque value See Section 3 2 2 for details Contact Extronics for replacement bolts Avertissements L...

Page 8: ...or N type RF connectors Good manual handling practice should be followed Warning User access Normal user access to the enclosure is through the cover plate and junction box Avertissements Acc s utili...

Page 9: ...rformed in accordance with IEC 60079 17 Important Before setting the units to work read the technical documentation carefully Important The latest version of the technical documentation or the corresp...

Page 10: ...XN3 Installation and Operating Manual 10 3 Installation 3 1 Mounting Mount the XN3 enclosure to a suitable structure using the mounting points shown...

Page 11: ...XN3 Installation and Operating Manual 11 Figure 1 Aluminium Enclosure Mounting Dimensions...

Page 12: ...rise the cover apart as it may damage the sealing gasket 3 2 2 Closing the Enclosure Inspect the gasket to ensure its sealing integrity If the front cover gasket is damaged it must be replaced Check a...

Page 13: ...rough the enclosure and are approved as part of the XN3 ATEX IECEx certification Apply suitably assessed glands to cable entries marked E and F as appropriate o Thread maximum size is M25x1 5 or 3 4 N...

Page 14: ...g point situated within the junction box Figure 4 Removal of the front cover plate is required to access the area Before putting in service Perform applicable electrical safety checks Visually check i...

Page 15: ...Installation and Operating Manual 15 3 5 Electrical Installation View inside junction box See Figure 6 and Table1 Figure 6 XN3 Internal Connections Showing All Options Interface Plate G F D E1 1 B E2...

Page 16: ...e 1 XN3 Internal Connection Features 3 6 Power Supply Input Connector The mains power connection is a phoenix socket on the PCB The plug part is Phoenix contact 1795789 It requires a minimum tightenin...

Page 17: ...plug as follows EIA 568B standard 3 9 2 Power Over Ethernet POE If Power Over Ethernet POE is used the format will depend on the access point installed in the XN3 Ensure that the correct Power Sourci...

Page 18: ...ay use different formats 3 9 4 2 Mini USB 3 10 Intrinsically Safe RF Outputs Refer to Figure 8 for location of Intrinsically Safe RF outputs 3 10 1 Example of RF threshold power calculation The follow...

Page 19: ...trinsically safe outputs Minimum IP54 connection Coaxial cable Notes Marking of iWAP XN3 must be observed when locating antenna in hazardous location Maintain 500Vrms isolation between conductive part...

Page 20: ...via a length of coaxial cable If antennas are sited remotely from the XN3 flameproof enclosure any metallic parts of the antennas must be isolated from earth by 500Vr m s to prevent hazardous earth c...

Page 21: ...familiar with the unit and must be aware of the regulation and provisions required for explosion protection as well as the relevant accident prevention regulations 4 3 Cleaning and Maintenance The XN3...

Page 22: ...g nut 3 and repeat the process 5 Repeat for the other side and the other rail 6 This is how the assembly looks when completed 7 Place the iWAPX3 on a protective surface as shown 3 8 Align both rails o...

Page 23: ...XN3 Installation and Operating Manual 23 6 Technical Data...

Page 24: ...ambient temperature ranges may be specified depending on the service temperature of installed equipment Alternative coding when Extronics iSOLATE501 is installed for DC isolation AII 3 1 G Ex ec ia Ga...

Page 25: ...temperature of installed equipment Alternative coding when Extronics iSOLATE501 is installed for DC isolation o Class I Zone 2 AEx ec iaGa nR IIC T6 Gc o Class II Zone 22 AEx iaDa tc IIIB T85o C Dc Al...

Page 26: ...079 7 5th Ed Standard for Explosive Atmospheres Part 7 Equipment Protection by Increased Safety e 2017 02 24 UL 60079 11 Ed 6 Explosive Atmospheres Part 11 Equipment Protection by Intrinsic Safety i 2...

Page 27: ...XN3 Installation and Operating Manual 27 9 EU Declaration of Conformity...

Page 28: ...XN3 Installation and Operating Manual 28...

Reviews: