Occupancy Sensor OCS 100W • Setup Guide (Continued)
Sensor Placement and Installation Options
When placing the sensor in a room, be sure the sensor is not aimed out through a door. The sensor can detect hallway traffic,
causing false triggers. PIR sensors trigger in response to changes in the amount of IR arriving from any of their segments of view
within a direct line of sight from the sensor. US sensors trigger in response to changes in the frequency of reflected ultrasonic
waves, caused by movement within the space.
NOTE:
on page 7 if you experience false triggers.
Installation Options
Rotation
60˚
80˚
Ceiling Mount
Wall Mount
Top View
Corner Mount
Sensor Placement
Wrong
Correct
Hallway
Figure 4.
Sensor Placement and Installation Diagrams
NOTE:
Mount the OCS 6 to 8 feet (1.8 to 2.4 m) away from HVAC vents and high air flow areas
Sensor Coverage
32'
(10 m)
23'
(7 m)
32'
(10 m)
23'
(7 m)
40'
(12 m)
20'
(6 m)
40' (12 m) Major
Motion Coverage
20' (6 m) Minor
Motion Coverage
10' (3 m)
Mounting
Height
Sensor Coverage
US Minor Motion
US Major Motion
IR Minor Motion
IR Major Motion
Figure 5.
Sensor Coverage Diagrams