Occupancy Sensor OCS 100W • Setup Guide

The OCS 100W is a dual technology occupancy sensor that can be used to automate meeting and presentation spaces when 
used with Extron control products. The OCS is equipped with ultrasonic (US), infrared (PIR), and photocell sensors that can be 
used together to report ambient light conditions and room occupancy. Sensors can be wired directly to Extron controller products 
equipped with Digital I/Os ports or via eBUS, when using optional eBUS interface accessories.
The OCS requires 24 VDC for operation. If local 24 V power is not available, use the included 12 V to 24 V power converter.

NOTE:

  The OCS 100W is designed to detect occupancy using both the PIR and US sensors with their default settings to 

avoid false detections.

Front Panel Features and Control

A

B

1
2

3
4

1
2

3
4

Blue Timer Test Button

Ultrasonic

Sensors

Infrared/Photocell 

Sensor and Fresnel Lens

Removable Front Cover

DIP Switches (B)

DIP Switches (A)

Ultrasonic (US) Green LED

(status indicator)

Infrared (PIR) Red LED

(status indicator)

Blue Photocell

Sensitivity Dial

Green Ultrasonic

Sensitivity Dial

Red Infrared

Sensitivity Dial

Notch

Figure 1. 

OCS 100W Front Panel Features

Figure 2. 

OCS 100W Controls

• 

Ultrasonic Sensors (2)

 — Detect movement in the room, based on ultrasonic sound waves. The US sensor emits ultrasonic 

sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are 
caused by the movement of people, which is detected by the US waves.

• 

Ultrasonic (US) Green LED status indicator

 — Flashes when the ultrasonic sensors detect occupancy.

• 

Infrared/Photocell Sensor and Fresnel Lens

 —

• 

The fresnel lens diffracts the incoming light and directs the light to the infrared sensor behind it. 

• 

The Infrared (PIR) sensor detects the presence of people based on the difference between the heat generated by moving 
people versus the ambient room temperature.

• 

Infrared (PIR) Red LED status indicator

 — Flashes when the infrared sensor detects occupancy.

• 

Removable Front Cover

 — Conceals all controls and DIP switches.

• 

DIP Switches (A)

 — 

A

Switch Function

OFF

ON

Note

1

Not used

*Not used

Not used

Switch is not used.

2

Occupancy 
detection 
behavior - Dual 
Technology Mode

*Mutually 
exclusive 
(requires both 
PIR and US 
detection)

Independent 
(either PIR or 
US detection)

If A2 is set to OFF, both the PIR and US sensors must 
be triggered (simultaneously) before the OCS reports an 
occupancy signal. If A2 is set to ON, the OCS reports 
occupancy based on only one of the sensors being 
triggered. When only one sensor is desired, set A2 to ON 
and adjust the dials accordingly. If A2 is ON, false detection 
when the room is not occupied increases.

3

Sensor status 
indicators

*LEDs enabled

LEDs disabled

Setting A3 to OFF provides a visual notification whenever 
the PIR or US sensors are triggered. When the visual LED 
indicators are a distraction or you want to disable the 
flashing LEDs, A3 should be set to ON.

4

Automatic adjust 
reset

*Retain 
learned sensor 
adjustments 

Erase all learned 
settings (toggle 
ON, then OFF) 

Only applicable when Timer (B3) or Sensitivity adjust (B4) or 
both are set to Automatic mode (OFF). Toggling A4 ON then 
OFF will reset any stored learned adjustments.

*Default and recommended settings

1  

2  

Summary of Contents for OCS 100W

Page 1: ...nic US Green LED status indicator Flashes when the ultrasonic sensors detect occupancy Infrared Photocell Sensor and Fresnel Lens The fresnel lens diffracts the incoming light and directs the light to the infrared sensor behind it The Infrared PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature Infrared P...

Page 2: ...too long for the OCS to turn off when the room is unoccupied adjust the timer to 8 or 4 minutes and extend the timer via the configuration of the connected control processor This setup reduces false detection Blue Timer Test Button To enable an 8 second timer test mode push the blue button once The test mode will last for 1 hour and then automatically resets to the dip switch settings To cancel th...

Page 3: ... the room or making movements throughout the room To avoid false detections when the room is unoccupied do not adjust the sensor too sensitively 4 Enter the room and verify if the US detector is detecting movement green LED flashes If the green LED flashes when entering the room the default green ultrasonic range dial is set correctly This sensor is very sensitive Verify the green LED flashes with...

Page 4: ...f reflected ultrasonic waves caused by movement within the space NOTE See Troubleshooting on page 7 if you experience false triggers Installation Options Rotation 60 80 Ceiling Mount Wall Mount Top View Corner Mount Sensor Placement Wrong Correct Hallway Figure 4 Sensor Placement and Installation Diagrams NOTE Mount the OCS 6 to 8 feet 1 8 to 2 4 m away from HVAC vents and high air flow areas Sens...

Page 5: ...n de sécurité TBTS de classe III Pull Cover Body Bracket Cover Wiring Harness Mounting Bracket Mounting Bolt Washer and nut 2 Insert wiring through Mounting Bracket Wall Building Wiring 1 POP Snap sensor onto mounting post 5 SNAP Push Replace Cover 7 Wall Wiring Harness Secure Mounting Bracket to the wall Connect building wiring to Wiring Harness with included wire nuts 2 3 Position Locking Screw ...

Page 6: ...P PRO 250 Control Processor Extron PC 1224 Power Module Extron OCS 100W Occupancy Sensor Occupancy Control Signal Blue Ground Black Ground Black 24 V Red 12 V Red Power Module 1 25 A MAX 75 mA MAX 1 5 A MAX PC 1224 33 2665 01 B www extron com 24V OUT 12V OUT 12V IN Ground all Devices External Power Supply 12 VDC 12 V Red Ground Black Extron ol Figure 8 OCS 100W Wiring Diagram Wire Connections Note...

Page 7: ... related topics see the Extron Safety and Regulatory Compliance Guide on the Extron website Power Attention ATTENTION These products are intended for use with a UL Listed LPS type power source Ces produits doivent être utilisés avec une source d alimentation de type LPS certifiée UL Use of a non LPS or unlisted power supply will void all regulatory compliance certification L utilisation d une sour...

Page 8: ...ity and related topics see the Extron Safety and Regulatory Compliance Guide on the Extron website 2017 2019 Extron Electronics All rights reserved www extron com All trademarks mentioned are the property of their respective owners Worldwide Headquarters Extron USA West 1025 E Ball Road Anaheim CA 92805 800 633 9876 ...

Reviews: