Step 3 — Connecting Cables

The ECM DIO8 can be powered by an eBUS connection to a control processor, distribution hub, or a 12 VDC power supply. Do 
not connect power to either unit until you have read these Attention notifications.

ATTENTION:

• 

Always use a power supply supplied or specified by Extron. Use of an unauthorized power supply voids all regulatory 
compliance certification and may cause damage to the power supply and the unit. 

• 

Utilisez toujours une source d’alimentation fournie ou recommandée par Extron. L’utilisation d’une source 
d’alimentation non autorisée annule toute certification de conformité réglementaire et peut endommager la source 
d’alimentation et l’unité.

• 

If not provided with a power supply, this product is intended to be supplied by a UL Listed power source marked 
“Class 2” or “LPS” and rated output 12 VDC, minimum 1.0 A.

• 

Si le produit n’est pas fourni avec une source d’alimentation, il doit être alimenté par une source d’alimentation 
certifiée UL de classe 2 ou LPS, avec une tension nominale 12 vcc et 1,0 A minimum.

• 

Unless otherwise stated, the AC/DC adapters are not suitable for use in air handling spaces or in wall cavities.

• 

Sauf mention contraire, les adaptateurs CA/CC ne conviennent pas à une utilisation dans les espaces d’aération ou 
dans les cavités murales.

• 

The installation must always be in accordance with the applicable provisions of National Electrical Code ANSI/
NFPA 70, article 725 and the Canadian Electrical Code part 1, section 16. The power supply shall not be permanently 
fixed to building structure or similar structure.

• 

Cette installation doit toujours être conforme aux dispositions applicables du Code américain de l’électricité (National 
Electrical Code) ANSI/NFPA 70, article 725, et du Code canadien de l’électricité, partie 1, section 16. La source 
d’alimentation ne devra pas être fixée de façon permanente à la structure de bâtiment ou à d’autres structures 
similaires.

NOTES:

• 

Connect up to eight eBUS devices for each IPCP Pro control processor.

• 

Wire the connectors in the same way at both ends.

• 

Do not exceed a total of 1000 feet (305 meters) of cable for connections between the IPCP Pro and all the eBUS 
devices.

• 

Do NOT power an ECM DIO8 from more than one power source. Power can be provided by an IPCP Pro control 
processor, a PS 1220EB power supply or an Extron 12 VDC power supply. If more than one power source is used in a 
system, make sure that the devices powered by the first source are isolated from the devices powered by the second 
source disconnecting the +V pin of the first source.

Up to eight devices can be connected to one control processor. In order for the control processor to be successfully configured, 
each device connected to the same control processor must have a unique six-bit, BUS ID, which is set with the DIP switch 
assembly on the front panel of the ECM DIO8 (see 

figure 1

A

, on page 1). If two or more modules have the same bus ID, 

address conflicts may prevent the panels from being recognized by the IPCP Pro control processor. If there is an address conflict, 
the status LED (see 

figure 1

B

) lights solidly (see 

Step 5 — Testing and Troubleshooting the System

 on page 12).

Connecting the eBUS cable

Connect eBUS port (see 

figure 1

C

, on page 1) to a control processor, a power supply, or another eBUS device using a 

standard eBUS cable. Before powering on the control processor, read the Attention notifications above. The four connectors are:

• 

+V

 (red*) — Carries 12 VDC power from the controller, active hub, or power supply

• 

+S

 (green*) — Carries the positive data signal

• 

-S

 (white*) — Carries the negative data signal

figure 11

• 

 

G

 (black*) and two drain wires — Ground

Extron STP20-2/1000 or STP20-2P/1000 cable is recommended 
for eBUS connections. If you use different cable, the wire color 
may be different.
The diameter of the ground wire and the two drain wires, when 
they are combined, is too large to fit into the captive screw 
holder on the eBUS terminal. Use a wire nut to combine a pigtail 
wire with the ground wire and the two drain wires. The pigtail is 
inserted into the eBUS connector in the usual way, as shown in 

figure 12

, on the following page.

eBUS

POWER LOAD

=3.6W

+V

+S
-S
G

Pigtail Wire
(Ground)

Wire Nut

" (5 mm) MAX.

3

16

Figure 11. 

Wiring the eBUS Cable

Summary of Contents for ECM DIO8

Page 1: ...US devices can be connected to one control processor Each eBUS device connected to the same IPCP Pro control processor must have a unique BUS ID which is set using BUS ID DIP switches see Step 2 BUS ID setup on page 6 B Status LED The ECM DIO8 has a three color LED red amber and green that provides diagnostic information about the connection communication and power status of the module see Step 5 ...

Page 2: ...n external switch or relay that has a voltage supplied The internal pull up resistor should be disabled by software GCP GS State On logic state Low Voltage 2 VDC GCP GS State Off logic state High Voltage 2 8 VDC 24 VDC max DIGITAL I O 1 2 3 4 G G 6 7 8 5 Figure 3 Digital Input Voltage Detection Digital output with Pull up Driving a Relay Coil Digital outputs can be used to power LEDs incandescent ...

Page 3: ...are Page 4 If the software appears at the top of the page click on the product see figure 7 1 which takes you to the product page on the Extron website This provides further information about the product Click Download and follow the on screen instructions to download the software 5 If you do not see the product use the or arrows 2 to see other options 6 If the product is not listed in the top sec...

Page 4: ... mounting with a junction box The ECM DIO8 can be mounted in any standard 1 gang junction box US Flex55 EU or MK The junction boxes must be purchased separately and installed by following the instructions provided by the manufacturer NOTE For the installation to meet UL requirements and to comply with National Electrical Code NEC the ECM DIO8 must be installed in a UL Listed junction box not inclu...

Page 5: ...e about 0 25 6 4 mm of the screw exposed 7 Fit the mounting bracket over the screw heads and slide the device up or down so that the screw is seated in the narrow slot of the bracket 2 8 Tighten the screws to secure the ECM DIO8 in place 3 9 Connect the cables as described in Step 3 Connecting Cables on page 9 e B U S S T A T U S G R E E N L I N K C O M E R R O R ID E R R O R A M B E R R E D v ECM...

Page 6: ...umbers for each of the DIP switches that are set to On to obtain the address of the device In figure 10 only DIP switch 5 is on and the rest are off which means the address for the device in figure 5 is 0 0 0 0 2 0 2 NOTES Any address can be used except address 0 binary 000000 which is reserved as the address of the controller Switch 1 on the left is the highest value 32 the most significant bit a...

Page 7: ...N M S B L S B 0 0 0 1 0 0 4 1 2 3 4 5 6 ON M S B L S B 0 1 0 0 1 1 19 1 2 3 4 5 6 ON M S B L S B 0 0 0 1 0 1 5 1 2 3 4 5 6 ON M S B L S B 0 1 0 1 0 0 20 1 2 3 4 5 6 ON M S B L S B 0 0 0 1 1 0 6 1 2 3 4 5 6 ON M S B L S B 0 1 0 1 0 1 21 1 2 3 4 5 6 ON M S B L S B 0 0 0 1 1 1 7 1 2 3 4 5 6 ON M S B L S B 0 1 0 1 1 0 22 1 2 3 4 5 6 ON M S B L S B 0 0 1 0 0 0 8 1 2 3 4 5 6 ON M S B L S B 0 1 0 1 1 1 2...

Page 8: ... 0 0 36 1 2 3 4 5 6 ON M S B L S B 1 1 0 1 0 1 53 1 2 3 4 5 6 ON M S B L S B 1 0 0 1 0 1 37 1 2 3 4 5 6 ON M S B L S B 1 1 0 1 1 0 54 1 2 3 4 5 6 ON M S B L S B 1 0 0 1 1 0 38 1 2 3 4 5 6 ON M S B L S B 1 1 0 1 1 1 55 1 2 3 4 5 6 ON M S B L S B 1 0 0 1 1 1 39 1 2 3 4 5 6 ON M S B L S B 1 1 1 0 0 0 56 1 2 3 4 5 6 ON M S B L S B 1 0 1 0 0 0 40 1 2 3 4 5 6 ON M S B L S B 1 1 1 0 0 1 57 1 2 3 4 5 6 ON...

Page 9: ...or Wire the connectors in the same way at both ends Do not exceed a total of 1000 feet 305 meters of cable for connections between the IPCP Pro and all the eBUS devices Do NOT power an ECM DIO8 from more than one power source Power can be provided by an IPCP Pro control processor a PS 1220EB power supply or an Extron 12 VDC power supply If more than one power source is used in a system make sure t...

Page 10: ...2 Connecting a Ground wire to the ECM DIO8 1 Cut about 2 51 mm from the end of the cable Save the ground wire for use as a pigtail 2 Remove about 1 25 mm of the jacket from the cable 3 Remove the shield to expose about 3 16 5 mm of each wire 4 Remove the shield to expose about 3 16 5 mm of wire at each end of the ground wire that was saved in step 1 5 Gather the pigtail wire with the ground wire a...

Page 11: ...US endpoint devices to the PS 1220EB Wire the connectors the same at both ends All ports are identical and interchangeable Power Input 100 240 VAC 50 60 Hz PS 1220EB ATTENTION Do NOT connect the power pin to any device that is already powered by the IPCP Pro control processor or by an additional power supply 3 16 5 mm Max Ground Signal 12 VDC Signal Ground Signal Signal X X Tie drain wires to grou...

Page 12: ...he sensor The ground G terminal of the ECM DIO8 must be connected to the ground terminal of the sensor and the voltage output 24 terminal of the ECM DIO8 must be connected to the voltage input terminal of the sensor The cable is not provided Step 4 Configuring the System Use Global Configurator Plus and Professional to configure the system or Global Scripter to program the system so that the syste...

Reviews: