Installing the VSP 8000 Series in an Equipment Rack
Note:
The instructions in this section apply to all switches in the VSP 8000 Series. The illustrations
show the VSP 8200 Series as an example, but the instructions apply to any switch in the series.
There are different ways to install a VSP 8000 Series switch in an equipment rack. Refer to one of
the following sections:
• Slide Rack Mount Kit-This is a separately ordered option that you can use to install your switch
in equipment racks that range from 300 mm to 900 mm deep. For installation instructions, see
Using the optional slide rack mount kit
• Brackets-The switch comes with brackets that you can install in one of two positions on the
chassis:
- Use the mid-chassis position for a two-post rack.
- Use the front panel position of the chassis for a four-post rack.
Caution:
It is highly recommended to mount the chassis on a tray designed for the specific rack and use
the Extreme Networks supplied rack mount brackets to hold the chassis in place. The chassis is
heavy and could cause damage to a rack if only the brackets are used, especially in a vibration
prone area.
For installation instructions, see
on page 68.
Before you begin
• Ensure that there is enough rack space to accommodate a 2 U switch (8.8 cm).
• The rack is bolted to the floor and braced if necessary.
• The rack is grounded to the same grounding electrode used by the power service in the area.
The ground path must be permanent and must not exceed 1 Ohm of resistance from the rack
to the grounding electrode.
About this task
Caution:
When you mount the device in a rack, do not stack units directly on top of one another. You
must secure each unit to the rack with the appropriate mounting brackets. Mounting brackets
cannot support multiple units. For a translation of this statement, see
on page 91.
Using the optional slide rack mount kit
The Universal Slide Rack Mount Kit is adjustable so that you can install your switch in equipment
racks of different sizes. Use the following procedures to install your switch in equipment racks with a
depth from 300mm to 900mm.
Installing the VSP 8000 Series in an Equipment Rack
March 2020
Installing the VSP 8000 Series