48VFL & 96VFL v1.2 07/13
OPTION LEVEL
CODE DESCRIPTION
RANGE
Default
Input type selection.
tYPE
RANGE(
℃
) RANGE(
℉
)
J
-50
~
1000
-58
~
1832
K
-50
~
1370
-58
~
2498
T
-270
~
400
-454
~
752
E
-50
~
750
-58
~
1382
B
0
~
1800
32
~
3272
R
0
~
1750
32
~
3182
S
0
~
1750
32
~
3182
N
-50
~
1300
-58
~
2372
C
-50
~
1800
-58
~
3272
D-PT
-200
~
850
-328
~
1652
J-PT
-200
~
650
-328
~
1202
LINE
-1999
~
9999
Refer to figure.
K
Unit of process value
:
Degrees C
:
Degrees F
: Engineer units for linear input
℃
Decimal point selection
0000
:
No decimal point
000.0
:
0.1 resolution
00.00
:
0.01 resolution, used for linear input only
0.000
:
0.001 resolution, used for linear input only
0000
000.0
00.00
0.000
0000
Output 1 control action.
: Reverse action for heating
: Direct action for cooling
Low limit of span or range. Set the low limit lower than the
lowest expected SV and PV display
Full range
0
High limit of span or range. Set the high limit higher than
highest expected SV and PV display
Full range
1000
Software filter.
0.0-99.9
10.0
Time scale for timer alarm.
Hours:Minutes;
Minutes:Seconds
00.00~99.59 00.00
Alarm 1 function. Refer to alarm section for details
If A1FU=None, the alarm function is cancelled
None, Hi, Lo,
dif.H, dif.L, bd.Hi ,
bd.Lo
t.on, t.oFF
Alarm 1 mode. Refer to alarm mode section for detail.
.
none, Stdy,
Lath, St.La
Alarm 2 function. Refer to alarm function section for detail
none, Hi, Lo, dif.H,