48VFL & 96VFL v1.2 07/13
RTD Input Specifications
RTD type
Platinum 100
(DIN or JIS)
RTD range
-328 to 1202
o
F (-200 to 650
o
C)
Break protection
Up- and down-scale
Lead wire effect
0.015
o
/ Ohm
Repeatability 0.2
o
C
Analog (Linear) Input Specifications
Current Input
4 to 20mA DC (2.7
input impedance)
Voltage Input
1 to 5V DC (>10M
input impedance)
Display range
-1999 to 9999 digits
Repeatability Within
1
digit
Relay and Pulse DC Output Specifications
Relay outputs
SPST (dry contact) relays can switch up to 5 Amps @ 110V AC or 24VDC (for resistive
loads only)
Pulsed DC outputs
0 to 24 VDC output (drives resistive loads to 250
max.)
Control actions
Indirect or reverse acting (heating) and direct acting (cooling)
Control types
ON/OFF control with Hysteresis (dead band)
Time proportioning control (for relay or pulsed DC output)
Standard proportional output (analog output)
Automatic tuning
Push-button activation. Automatically tunes the proportional band and integral/derivative
times.
Manual Tuning
Proportional Band (Pb): 0.0 to 300.0% of Full Scale
Integral time or ‘Reset’ (Ti): 0 to 3000 seconds (includes anti-reset wind-up)
Derivative time or ‘Rate’ (Td): 0 to 900 seconds
Cycle Time: 0 to 100 seconds (set to ‘0’ for 4-20mA output)
Hysteresis: 0.0 to 25.5% of Full Scale
ALARM Output Specifications
Alarm relay outputs
SPST, dry contact relay can switch up to 3 Amps @ 110VAC; (for Resistive Loads)
Alarm modes
Deviation, Absolute, and Band Alarms with dead band (Hysteresis) adjustment.
ANALOG Output Specifications
Analog output
4-20mA DC
Load limits
600
max.
Programming
Set Cycle Time (Ct) to ‘0’ to enable the analog output