Applications 

Measuring Power Tools and Small Appliances 

For small appliances, connect the Black (EARTH) lead to conductors and the Red (LINE) 
lead to insulating material. 
 
For single or double insulated power tools, one lead should be connected to the device’s 
chuck, blade, etc. and the other lead to one of the AC power cord conductors (test both 
conductors in turn). Refer to the power tool application diagram below. 

 

 

 

 

 

 

 

Testing Motors  

AC Motors 
Disconnect the motor from the line by: 

a. Disconnecting the wires from the 

motor terminals or 

b. Opening the main switch 

If the main switch is opened, and the 
motor also has a motor-starter, then 
the starter must be held in the ON position. With the main switch opened, the measured 
resistance will include the resistance of the motor wire and all other components between 
the motor and the main switch. If a weakness is indicated, the motor and other 
components should be checked individually. If the motor is disconnected at the motor 
terminals, connect the RED lead to the grounded motor housing and the BLACK lead to 
one of the motor leads. 
DC Motors 

1.  Disconnect the motor from the line. 
2.  To test the brush rigging, field coils and armature, connect the RED lead to the 

grounded motor housing and the BLACK lead to the brush on the commutator. 

3.  If the resistance measurement indicates a weakness, raise the brushes off of the 

commutator and separately test the armature, field coils and brush rigging by 
connecting one lead to each individually, leaving the other connected to the grounded 
motor housing. This also applies to DC Generators. 

Testing Single Conductor Cables 

1.  Completely disconnect the cable 

under test from its source and 
destination. 

2.  Connect the test leads to the 

cable as shown at right. 

Core          Insulation   Sheath    Covering 

EARTH        GUARD    LINE 

AC 
Plug 

For 2 or 3 prong plugs, connect the 
RED lead to one conductor at a time 

Connect the BLACK 
lead to the chuck 

Connect RED lead 
to grounded housing 

Connect BLACK lead 
to the motor leads 

Summary of Contents for 380375

Page 1: ...User s Manual Digital High Voltage Insulation Tester Model 380375 ...

Page 2: ... be liable for any direct indirect incidental or consequential damages Extech s total liability is limited to repair or replacement of the product The warranty set forth above is inclusive and no other warranty whether written or oral is expressed or implied Introduction Congratulations on your purchase of Extech s High Voltage Insulation Tester This device has four voltage test ranges up to 5kV a...

Page 3: ...inutes Enersave TM mode Shorter test time to conserve battery life Operating conditions 32 to 104 o F 0 to 40 o C 80 RH Storage conditions 14 to 140 o F 10 to 60 o C 80 RH Dimensions 4 7 x 6 7 x 3 7 120 x 170 x 95mm Weight 1 94 lbs 880g Range Specifications Test Voltage Resistance Ranges Short Circuit Current Accuracy Resolution 500V DC 0 to 25 GΩ 1mA 1000V DC 0 to 50 GΩ 1mA 2500V DC 0 to 125 GΩ 1...

Page 4: ...s and then stop at the Select Test display 3 Select the desired test voltage by pressing the 500V 1KV 2 5KV or 5KV button The screen will briefly display the selected test voltage and then will proceed to the Connect Leads Testing for LIVE display If the circuit is live the display will indicate Live Warning Circuit Live and the meter will beep If this occurs remove the test leads and press the ON...

Page 5: ...is is particularly useful in determining whether an insulating material under test will break down in a given amount of time Manual Test STOP To stop a test in progress press the ON TEST button The test will immediately end and the system will automatically discharge Automatic Test STOP The test automatically stops after 100 seconds if the meter is not in the Enersave TM mode When in the Enersave ...

Page 6: ...her components should be checked individually If the motor is disconnected at the motor terminals connect the RED lead to the grounded motor housing and the BLACK lead to one of the motor leads DC Motors 1 Disconnect the motor from the line 2 To test the brush rigging field coils and armature connect the RED lead to the grounded motor housing and the BLACK lead to the brush on the commutator 3 If ...

Page 7: ...ow will completely test a single phase transformer Note that at least 1 minute should be allowed between each test 1 High voltage winding to low voltage winding and ground 2 Low voltage winding to high voltage winding and ground 3 High voltage winding to low voltage winding pictured below 4 High voltage winding to ground 5 Low voltage winding to ground Testing one conductor to all of the conductor...

Page 8: ...ry compartment cover 5 Replace the eight batteries ensuring proper polarity 6 Affix the rear cover and secure the rear screw Cleaning Periodically wipe the case with a dry cloth Do not use solvents or abrasives to clean this instrument Repair and Calibration Extech offers complete repair and calibration services for all of the products we sell For periodic calibration NIST certification or repair ...

Reviews: