5.3 Step 3: Start the Discharge Test Timer & Take Up to (7) Sets of Cell Discharge
Readings
(i)
Ensure the DLV40 USB cable is
DISCONNECTED
(ii)
Turn the DLV40
ON.
(iii)
If
NOT
in
“Discharge Test”
mode:
B.
If not in Main Menu, press the
“MENU”
button
twice
to enter the Main Menu:
(vii)
Use the “
UP”
or “
DOWN”
buttons to scroll to Discharge Test Mode:
(viii)
Press
“ENTER”
to select.
(iv)
Ensure String A (Float Voltages) is selected and appropriate float cell voltage data has
already been recorded.
Dischg
Float
+0.000
A:011
024.5
Current Test Mode
Selected String (“A”)
and
next reading
in the
selected string (“011”).
Sum of cell voltages
for the selected string
Discharge Time
*** Main Menu***
MODE : 8 by 256
*** Main Menu***
MODE : DISCHARGE
For example, if (10) cell float voltage readings of average ~ 2.45 had previously been
recorded, the DLV40 display should match the above.
The DLV40 USB cable
MUST
be
DISCONNECTED
whenever measuring voltages!