(vi)
Repeat steps (iv) and (v) until all cell voltages in the string have been measured.
For
“20x48”
or
“8x256”
modes, please refer to
Section 6.0 to for the Float Test Procedure(s)
.
For
“Discharge Test”
mode, please refer to
Section 5.0 to for the Discharge Test Procedure
.
3.1
Over Voltage Indication (ALL Modes)
The DLV40 provides both an audio and visual indication if the probes are connected to an
excessive input voltage (Vin < -19.999 VDC or Vin > +19.999 VDC)
The unit will
beep
continuously and display:
This warning is removed as soon as the probes are disconnected from the high voltage source.
In
“Discharge Test”
mode:
-
The
string capacity of the discharge strings
(B through H) is
limited
to the number of
readings in
float string
(String A).
-
Once the last discharge reading is taken, (strings B through H), the DLV40 will automatically
increment to the next string.
-
The user then must wait for the required test interval before taking the next set of discharge
cell voltage readings. The required test interval is typically ~Discharge test length divided by
(7)
OVER VOLTAGE!!!