10
MANUGENEX7xx - Version 2.12
© 2018-2022 EXOR International S.p.A. - Subject to change without notice
3 Technical Specifications
Voltage dips, short interruptions and
voltage variations immunity test
Port: AC mains; Level:
100% duration:
1 cycle and 250 cycles (50Hz);
1 cycle and 300 cycles (60Hz);
40% duration:
10 cycles (50Hz);
12 cycles (60Hz);
70% duration:
25 cycles (50Hz);
30 cycles (60Hz);
Phase: 0°-180°
Test executed on the 230Vac side of the Exor International S.p.A. Power Supply EN 61000-4-11
Port: DC mains; Level:
0% duration:
10ms 20 spaces by 1s
Test executed on the 24Vdc of the EUT
EN 61000-4-29
Durability information
Backlight service life
40000 Hrs. or more
(LED type)
(Time of continuous operation until the brightness of the
backlight reaches 50% of the rated value when the
surrounding air temperature is 25°C) - see
Note 1
Note 1
: Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.
Surface resistance
Chemical resistance of the front glass for an exposure time of 24 hours without visible changes:
• Betadine (10% Povidone Solution)
• Cola
• Electrode Gel/Paste
• Hydrogen Peroxide (3% Solution)
• NaCl (0.9% Solution)
• Coffee
• Dextrose (5% Glucose Solution)
• Hydrogen chloride (0.5% Solution PH=1)
• Isopropyl Alcohol
• Sodium Hypochlorit
• Ethyl Alcohol (70%-90%)
• Quaternary ammonium compound