Exodraft EBC10 Instructions For Fitting, Installation And Operation Download Page 24

3.1.3 

Alarm overview

The table below presents an overview of the alarms that may occur (the alarm numbers are displayed in the alarm 

menu).

Alarm

Error type

Solution

A00

No error

A01

XTP flow alarm.

Defaults (menu 23):

Chimney fan: < 64% of set pressure

Air supply fan: > 300% of set pressure

Check:

The flue, the chimney and the chimney fan for  

blockages.

The commissioning.

That the measuring probe and the spigots on the 

pressure transducer are not blocked.

A02

PDS check error

Check:

The setting of the monitoring unit (the PDS).

The connection to the PDS.

The PDS’s switch function.

A03

PDS error (flow error)

Check that:

The PDS is connected.

The PDS is correctly adjusted in relation to the set point.

Menu 31 has been set correctly (1).

A04

XTP Start Timer error (flow error)

Check:

the hose to the pressure transducer.

the commisioning.

the chimney fan is of sufficient capacity.

A10

XTP not connected

A11

PDS not connected

Check the PDS connection.

A13

AUX alarm (alarm for terminals 26–28)

Check:

the connections to terminals 26–28.

the setting in menu 31 (2)

the loop between terminals 26 and 28. 

If XTP is connected : power off/on the unit. 

If error persist contact dealer (defective unit).

A14

Temperature sensor not connected

A16

24 VDC overloaded

Check: 

the load on terminals 19-20.

If error persists, contact dealer (defective unit).

A17

XTP connected (error only for the 2-stage 
speed regulation function  

)

Remove the XTP. The XTP must not be fitted in speed-

regulation mode.

A18

XTP overload

Check if XTP is defective.

A81

E2prom read failure

Reset to defaults (menu 18).

Turn the EBC10 off.

Restart again. 

If error persists, contact dealer (defective unit).

A82

Error in Safety relay circuit 

A83

Error in Safety relay circuit 

A84

Error in Safety relay circuit 

A85

Safety No HeartBeat

A86

Safety input circuit error

A87

Safety input circuit error

A88

Safety input circuit error

A89

Faulty heartbeat from safe processor 

detected

A98

Faulty main processor

Reset to defaults (menu 18).

Turn the EBC10 off.

Restart again. 

If error persists, contact dealer (defective unit).

A99

Faulty main processor

3120049-EBC10-UK

24

 • List of alarms and troubleshooting

Summary of Contents for EBC10

Page 1: ...Instructions for fitting installation and operation UK EBC10 EBC10 ALARM RESET OK Read and save these instructions...

Page 2: ...6 2 4 1 Single boiler application 17 2 4 2 Single boiler application with potential free contact in boiler 18 2 4 3 Single boiler application with extra fail safe protection using PDS 19 2 4 4 Solid f...

Page 3: ...ions contact the supplier at the address or telephone number listed on the back of the manual Before servicing or cleaning the unit switch off at service panel and lock service panel to prevent power...

Page 4: ...section 2 Pressure controlled regulation of exodraft fans factory set Read sections 3 5 Section 2 Pressure controlled regulation of exodraft chimney fans default The EBC10 ensures and monitors consta...

Page 5: ...oor installation E 2 m silicone hose 2000335 Supplies the pressure transducer XTP with reference pressure from the measuring probe or from outdoors Instructions 3120049 Instructions for fitting instal...

Page 6: ...from being formed The EBC10 should be mounted in a way that protects it against rain snow Note Special aspects if you require positive pressure in the chimney boiler room Connect the hose to the posit...

Page 7: ...keep water out If the pressure transducer is positioned in a place where insects have access to the free end fitting a sinter filter is recommended 1 4 Layout of the user interface 1 4 1 Panel EBC10...

Page 8: ...A AC3 red the relay is open 11 12 BOILER 1 IN 18 230VDC VAC green the input is active 13 14 BURNER 1 OUT 250VAC 4A AC3 green the relay is connected 15 16 BOILER 2 IN Not active 17 18 BURNER 2 OUT Not...

Page 9: ...ney fan 7 Symbol for pressure controlled regulation of exodraft chimney fan 8 Symbol for pressure controlled regulation of exodraft supply air fan 9 Symbol indicating PDS error PDS check flashing 10 O...

Page 10: ...by qualified technical staff Layout of the user interface The user interface is operated through four buttons with the following functions Button Function Activate the user menu Edit and save setting...

Page 11: ...lays the actual pressure in this example 30 Pa 2 Briefly press to enter the user menu 3 Press Press and until the required pressure appears in the lower display 4 Press OK to confirm the setting 5 To...

Page 12: ...set point for this menu being shown in the lower display pos 13 on page 9 Menus whose last digit is 0 are exit menus These are used to navigate one level back To do so press OK To activate the editin...

Page 13: ...ion x xx x xx x xx 15 Select XTP measurement range 150 Exit 151 Set Low XTP value from 500 Pa to 0 Pa 0 Pa N A 0 Pa 152 Set High XTP value from 0 Pa to 500 Pa 150 Pa N A 150 Pa 16 Positive negative pr...

Page 14: ...Set proportional amplification 0 2 to 5 2 2 N A 1 2 352 Integration time Ti Set integration time from 1 to 30 s 5 N A 3 353 Differential time Td Set differential time from 1 to 30 s 1 N A 5 354 Sample...

Page 15: ...to go to menu 10 3 Press to go to menu 11 Press OK 4 Press until the symbol and number for the opera ting function you require is displayed The three opera ting functions are 1 Pressure controlled reg...

Page 16: ...outputs are linked to light emitting diodes for the monitoring and service of the system 1 4 2 Light emitting diodes and terminal board page 8 2 3 Electrical connection This work must be performed by...

Page 17: ...the boiler Connect the burner start signal L to terminal 11 Connect the neutral wire to terminal 12 The start signal for the burner is sent from terminal 14 Loop terminals 11 and 13 Connect the chimn...

Page 18: ...to terminals 1 3 Connection to the boiler Connect the potential free contact to terminals 11 19 Loop terminals 12 20 Connect the burner start signal to terminals 13 14 Connect the chimney fan to term...

Page 19: ...ge to terminals 1 3 Connect the burner startsignal to terminal 12 The start signal to the burner comes back on terminal 14 Connect the burner start signal to terminal 11 Loop terminals 12 and 13 Conne...

Page 20: ...iler Connect the burner start signal L to terminal 11 Connect the neutral wire to terminal 12 Loop terminals 11 and 13 The start signal from the burner comes from terminal 14 Connect the ventilator to...

Page 21: ...enu items 1 4 in the same way as shown in the example in page 11 To operate menu items 1 4 use the buttons as follows Step Press To 1 OK Activate the user menu 2 and Go to the menu item you wish to ed...

Page 22: ...om step 1 4 Check that the monitoring system shuts off the boiler To simulate an error situation disconnect the hose from the pressure transducer XTP Burner is switched off diode switches off and the...

Page 23: ...reset In the event of an alarm undertake the following procedure Step Action 1 Go to menu 4 menu 5 for operating function 2 to display the current alarm 2 Check the alarm overview next page to identif...

Page 24: ...erminals 26 28 Check the connections to terminals 26 28 the setting in menu 31 2 the loop between terminals 26 and 28 If XTP is connected power off on the unit If error persist contact dealer defectiv...

Page 25: ...LEDs Remove the front panel This work must be performed by a qualified electrical engineer 3 2 2 Communication error If the display shows three horizontal lines in the lowest display box Press RESET a...

Page 26: ...igital inputs BOILER 1 IN 18 to 230 VAC VDC Pressure sensor input XTP IN 0 to 10 VDC 20 mA Pressure switch input PDS IN 24 VDC 20 mA Temperature sensor TEMP IN 30 C to 500 C Outputs Digital output rel...

Page 27: ...iften uit de hieronder genoemde normen en standaards som omfattas av denna deklaration verensst mmer med f ljande standarder jota t m selvitys koskee on seuraavien standardien mukainen sem eru me tali...

Page 28: ...info exodraft se www exodraft se NO exodraft a s Storgaten 88 NO 3060 Svelvik Tel 47 3329 7062 Fax 47 3378 4110 info exodraft no www exodraft no UK exodraft Ltd 10 Crestway Tarleton GB Preston PR4 6B...

Reviews: