UK |
19
3112009_CFIR_UK
CFIR300, CFIR400, CFIR500
CFIR300, CFIR 400 and CFIR 500 requires 3 x 400 V AC from the factory. They can be configured for 3 x
230 V AC using the diagram below.
The diagram shows the correct wiring in the connection box on the motor.
Wiring diagram – CFIR300, CFIR400 & CHIR500
2U
2V 2W
1U
L1
1V
L2
3 x 400 V
1U 2W
1V
2U
L2
1W 2V
L3
3 x 230 V
L1
1W
L3
Wiring diagram – CFIR300, CFIR400 & CHIR500
2U
2V 2W
1U
L1
1V
L2
3 x 400 V
1U 2W
1V
2U
L2
1W 2V
L3
3 x 230 V
L1
1W
L3
Inline fan and motor specifications can be found under
Dimensions
.
The Inline fan is equipped with a variable speed motor.
Use cable gland size M25 at the junction box on the motors.
Isolation switch
In accordance with the provisions of the applicable EU Machinery Directive a chimney fan must always have
an isolation switch fitted. The isolation switch must comply with national wiring standards, and it must be
ordered separately, as it is not part of the standard Exodraft scope of delivery.
Checking and changing rotation of impeller
To check the rotation of the impeller, the rotation of the cooling
vanes at the end of the motor housing must be observed at low
rpm.
The cooling vanes can be observed through holes in the end
cover of the motor. Correct rotation direction is indicated by an
arrow on the Housing in front of the motor as illustrated.
It is possible for the fan to operate with improper rotation, cau
-
sing the fan to be limited to 25-30 % of full capacity. Improper
rotation damages the motor, and causes various electrical faults
at the variable frequency converter.
Change of rotation is carried out by changing two of the wires at
the frequency converter. See wiring diagram delivered with the
frequency converter.
B
Fig 11, side 11
DANGER
Turn off electrical power before servicing. Contact with live electric components can cause shock or death.