Installer menu
Store functions
Description
Shown only if reg. type
Standard
is selected.
Select Heat 1 regulation type
Select
Standard
if
Heat1
is to be regulated as a single
heating surface.
Shown only if reg. type
Splitter
is selected.
Select Heat 1 regulation type
Select
Splitter
if Heat1 is to be regulated as 2 heating
surfaces connected in sequence =
Heat1
and
Heat12
●
Set exit signal
Heat 12
[0-10V/2-10V]
●
Read off current exit signal for
Heat 12
[V]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
●
Mark to activate the function
●
Set delay for condenser [s]
●
Read off current condenser delay [s]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
●
Set min active time for
Heat 12
●
Read off current active time for
Heat 12
●
Mark for activation of rise/fall time
●
Set min rise/fall time [Sec]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 12
●
Mark to activate hysteresis
Heat 1
●
Set hysteresis for relay
Heat 1
[%]
Shown only if reg. type
Splitter
is selected.
Set reg. parameters for exit Heat 1
●
Mark to deactivate
Heat 1
Shown only if reg. type
Copy
is selected.
Select Heat 1 regulation type
Select
Copy
if
Heat 1
is to be regulated as 2 heat surfa-
ces connected in parallel.
Set limits for Heat 2
In many cases
Heat2
is an electrically heated surface. To
save energy from this heat source, the control system
may be set to automatically reduce use of this heat
source, depending on the deviation from room tempera-
ture or depending on outdoor temperature.
Set limits for Heat 2
●
None - no limits for
Heat 2
Shown only for
Room
temperature
limitation
Room temperature limits
●
Set temperature difference (setpoint/current) [°C]
●
Connection degree per step [%]
●
Read of Temperature (setpoint/current) [°C]
3005263-2015-08-20
Installer level
22/52