6.3 Cooling/heating coils (DX)
VEX310T-350T
Data
310T
320T
330T
340T
350T
Weight without fluid [kg]
4
7
10
12
21
Fluid content [l]
0.44
0.72
1.26
1.77
2.8
Number of pipe rows
4
4
4
4
4
Number of circuits
3
5
8
12
16
Fin spacing
2.5
2.5
2.5
2.5
2.5
Face area (h x b) [mm]
200 x
350
200 x
620
300 x
685
450 x
685
625 x
740
Connection dimension
DN15 (1/2")
Test pressure [kPa]
4500
Max. oper. pressure [kPa]
4200
6.4 Panel filters
6.4.1 Filter data
Filter class according to
ISO 16890
Coarse
65%
ePM
10
[65%]
ePM
1
55%
ePM
1
80%
VEX size/Data
310T panel h x b [mm]
312 x 453
320T panel h x b [mm]
312 x 723
330T panel h x b [mm]
363 x 794
340T panel h x b [mm]
471 x 794
350T panel h x b [mm]
614 x 850
Panel thickness [mm]
48/96
48/96
48/96
96
Filter class according to
EN 779
G4
M5
F7
F9
Temperature resistant to
70°
EUROVENT certification is only valid if original filters are used. For more details