6.3 Bag filters
Pressure loss graph
for M5 and F7 filters
Filter data
FB260M5
FB260F7
Filter area
1 x 2.5 m²
1 x 3.0 m²
1 x 4.0 m²
1 x 5.0 m²
Face area (h x w)
1 x 592 x 490 mm
1 x 592 x 592 mm
1 x 592 x 490 mm
1 x 592 x 592 mm
Total number of bags x depth
1 x 5 x 380 mm
1 x 6 x 380 mm
1 x 5 x 380 mm
1 x 6 x 380 mm
Filter class
M5
F7
Retention degree according to EN779
96%
> 99%
Efficiency
45%
85%
Volume flow rate
5,000 m³/h
5,000 m³/h
Initial pressure drop
64 Pa
97 Pa
Recommended final pressure drop at
normal volume flow rate
164 Pa
197 Pa
Temperature resistant to
70°C
70°C
EUROVENT certification is only valid if original filters are used. See under section
5 Maintenance, for more details about original filters.
3003434-2014-04-14
Technical data
30/34