6. Technical data
6.1 Weight, corrosion class, temperature range, etc.
Weights
The total weight of the unit
525 kg
Unit without doors, fan section and base (for internal transport)
361 kg
Fan section (of which fan unit 2 x 33 kg)
Rotor section
2 x 117 kg
128 kg
Doors, fan section
Door, rotor section
2 x 16.5 kg
10 kg
Base
55 kg
Corrosion class
Corrosion class
Corrosion class C4 in accordance with EN ISO 12944-2
Temperature range
Outdoor air temperature
-20ºC to +35°C
Though supply air only
+10ºC to +35ºC
Ambient temperature
-30ºC to +50ºC
HMI panel
Ingress protection
IP20
Ambient temperature
0°C - +50°C
Fire thermostats
Cut-out temperature, BT70
70°C
Cut-out temperature, BT50
50°C
Cut-out temperature, BT40
40°C
Max. ambient temperature, sensor
250°C
Ambient temperature, thermostat housing
0°C - +80°C
Sensor length
125 mm
Ingress protection
IP40
3003434-2014-04-14
Technical data
27/34