5.4.4 Cleaning the crossflow heat exchanger
Step
Action
1
Switch off the power supply to the unit at the isolation switch before opening
the door.
2
remove the baffle plate for condensate.
3
Remove the plug from the bypass motor. Hold down the split pin under the
plug with a screw driver, see photos:
4
Dismount the Tice sensor from the heat exchanger bracket (see photo step
12).
5
Remove the crossflow heat exchanger, see section "Removal of crossflow
heat exchanger".
6
Press the release button on the bypass motor and turn the damper with the
louvres in open position.
7
The bypass motor must be dismounted before cleaning the heat exchanger
with water, see photos:
Do not activate the release button on the bypass motor while
it is dismounted, as this will alter the position of the motor
compared to the damper.
8
Clean the heat exchanger by flushing with hot water or by pressure wash-
ing. Max. water temperature. 90
℃
.
9
Mount the bypass motor. The damper must be in open position (louvres
fully open), as for dismounting.
10
Shut the louvres, and replace the heat exchanger.
3004513-2016-01-14
Maintenance, hygiene and servicing