OJ GreenZone™ Module MP-Bus
English
Type
Product
ETF-1098L1-4
PT1000 duct sensor (°C)
ETF-998-H
PT1000 room sensor (°C), 80x80 mm
Products from other suppliers
Type
Product
Belimo LMV-D3-MP, NMV-D3-MP,
CMV-XXX-MP
VAV damper actuator MP-Bus
Belimo CQ24A-MPL, LR24A-MP,
NR24A-MP, SR24A-MP
Heating valve actuator MP-Bus
Belimo CQ24A-MPL, LR24A-MP,
NR24A-MP, SR24A-MP
Cooling valve and combination heating/cooling
actuator for MP-Bus
050-8-0004 eSENSE Duct
CO2 sensor for duct mounting
Thermokon TFR 1,8, TFR 1,8-R
Frost thermostat with 1.8 m capillary tube
Thermokon WRF06I / RDI
Motion sensor for surface mounting
Telephone cable, type: TD6006 Black
Telephone cable, 6-core, make: INEC
TE Connectivity telephone connector, RJ12
Modular telephone conn. 6/6, RJ12 standard conn.
INSTALLATION
OJ GreenZone™ Module MP-Bus should be fitted to a standard 35 mm DIN rail mount-
ed in an enclosure corresponding to the installation site classification (see fig. 2 for unit
dimensions). The unit itself is classed as IP20 and ETT-KH from OJ Electronics can be
used for such covering purposes. The most practical location will often be in the vicinity
of other components, valves, sensors, etc. associated with the VAV zone. An overview
of the physical configuration of the system is given in fig. 19.
An ideal location would be above a suspended ceiling panel. OJ GreenZone™ Module
MP-Bus must be provided with a 24 VAC, +/-15% power supply and is therefore
equipped with looping terminals (max. 1.5 mm
2
) for the purpose (see figs 8 and 9).
Other connections are made by means of a combination of RJ12 connectors and screw
terminals for connecting wires of max. 1.5 mm
2
cross-sectional area (see fig. 3).
Connections and indications
(see overview in fig. 1)
In fig. 3, all connectors are marked with a letter (A – P).
See below for descriptions of electrical connection of the various components, inputs
and outputs, and other signals and indications of the OJ GreenZone™ Module MP-Bus.