Program example
5.2.2.1 Weekday
1 IAQ. level >
1 Time of day >
2 IAQ. level >
2 Time of day >
3 IAQ. level >
3 Time of day >
4 IAQ. level >
4 Time of day >
5 IAQ. level >
5 Time of day
Standby
06:00
Comfort
07:30
Economy
17:30
OFF
00:00
Inactive
--:--
Time interval
Indoor air quality level
06:00 - 07:30
Standby
07:30 - 17:30
Comfort
17:30 - 00:00
Economy
00:00 - 06:00
OFF
Menu 7 - Safety functions
Menu 7.1 - Fire alarm
Four operating
modes
There are four different operating modes in the event of a fire. The selected oper-
ating mode must meet regulatory standards.
Go to Menu 7.1 and select mode
Operating mode
VEX308
Internal damper BP*)
1 (factory setting)
Supply air and extract air stopped
BP1 closed
2
Supply air 100% and extract air stopped
BP1 open
3
Supply air stopped and extract air 100%
BP1 closed
4
Supply and extract air 100%
BP1 open
*) BP1 = Bypass damper 1
Activation of oper-
ating mode
The selected operating mode under the function "Fire alarm" is activated if the
closed circuit in any of the two inputs EXact2: Fire and AUX In on EXact2 main
board are broken.
The inputs allow the connection of:
● Smoke detectors
● Fire thermostats (e.g. BT40, BT50 or BT70)
● BMS
● Fire control system
If an input is not used, a jumper must be used.
3006401-2022-05-04
Starting up the unit for operation
37/72