MCCW control
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers, sen-
sors, air directions, etc.)
xx
yy
z
31
01
1
Module configured in-
correctly. Check CN6
on PCB
●
Check the jumper in the CN6 connector on the cooling control
circuit board. There must be a jumper across 4 and 6, and
across 5 and 6.
31
06
1
Cooling control current-
ly run locally due to
service
Cooling control temporarily controlled by Lodam Multi Tool. Override
lasts for max. 60 minutes
31
07
1
Cooling control safety
functions overridden lo-
cally due to service
Cooling control temporarily controlled by Lodam Multi Tool. Override
lasts for max. 60 minutes
31
13
4
Cooling control detec-
ted but not selected in
VEX configuration
The cooling unit is configured in menu 3.4 "Accessories".
31
14
4
Cooling control config-
ured incorrectly in con-
nection with selected
VEX configuration
●
Check the jumper in the CN6 connector on the cooling control
circuit board. There must be a jumper across 4 and 6, and
across 5 and 6.
31
15
4
No modbus communi-
cation to cooling control
●
Check the modbus cable between the connection board and the
MCCW module
●
Check the modbus cable from the MCCW module to the other
units for faulty wiring
3004256-2014-09-10
Alarms
62/72