Alarm code
If an alarm has been generated, an alarm code is shown in the display in the format
XXYYZ, where .
XX = unit
YY = fault code
Z = category of alarm. See category table in this section.
16 alarms
There can be up to 16 alarms on the "Current list". The first alarm to be added to
the queue will be the first alarm to be removed, if there are more than 16 alarms
(FIFO principle).
Info in EXact
shown only in the alarm log list Menu 4.6
Example - list of
alarms
36024 is an alarm on EC controller 1 (
36
024). Alarm description is
"The supply
voltage to the EC controller is too low"
(36
02
4). The category is critical (3602
4
).
##/nn
XXYYZ
Any active alarm is shown under the alarm symbol. If there is more than one alarm,
each individual alarm is shown for two seconds on a rotation basis.
- ##/nn = alarm no. "##" out of total number "nn" of alarms.
- XXYYZ see definition for alarm number.
Category
Category (Z)
Alarm level
Effect on operation
Icon
1
Info
Operation continues
2
Warning
Operation continues
3
Alarm
Operation continues but with reduced
functionality
4
Critical
Operation stops
5
Fire
Triggered fire alarm procedure mode
starts
Find troubleshooting directions in the list of alarms via the alarm number.
Alarm log list - Menu
4.6
A letter is shown following the alarm or info code:
C = Clear
S = Set
The alarm log list shows the latest 100 alarms, warnings and past information.
The first alarm/info to be added to the queue will be the first to be removed, if there
are more than 100 of them (FIFO principle).
Delete alarm log
The alarm log can be deleted by selecting "Yes". This action cannot be reversed.