background image

INSTALLATION

Mounting the Thermostat

ATTACH THE MOUNTING BRACKET TO THE WALL

 

1. Place the bracket on the wall where you would like 

the thermostat to be and mark the two holes with a 

pencil.

2. Using a 3/16” drill bit, drill out the marks you just 

made on the wall.

3. Insert the wall anchors into the holes pressing flush 

with the wall.

4. Place the bracket over the holes and fasten with the 

supplied #8 screws. 

The installer should be an experienced and trained 

HVAC contractor. Failure to read and follow 

instructions carefully before installation or 

operation could damage this control or cause 

property damage. Test the finished installation for 

proper operation.

Mount the EWT-3900 Thermostat about 5 feet 
above the floor in an area with good air circulation 
and average temperature. DO NOT install the 
thermostat where it can be affected by:

drafts or dead spots behind doors and in  
corners
hot or cold air from ducts
radiant heat from sun or appliances
concealed pipes and chimneys
on surfaces such as an outside wall, that 
are a different temperature than the room 
air temperature. 

Mounting the Receiver

Mount the receiver with the supplied mounting 

screws near the zone control panel or HVAC 

equipment to be controlled. 

Do not mount the 

receiver inside the equipment cabinet or any 

other metal enclosure. Do not Mount the 

receiver in any location than is subject to 

freezing and/or condensation.

EWC Controls Inc.   385 Highway 33   Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362     E-Mail- [email protected]

2

CAUTION

!

To prevent electrical shock and/or equipment damage, 
disconnect electric power to HVAC system at main
 fuse or circuit breaker box until installation is complete.

WARNING

!

Do not use circuits exceeding specified voltage.  Higher
voltage will damage control and could cause shock or
fire hazard. 

Do not short out terminals on gas valve or primary control
to test.  Shorted or incorrect wiring will damage thermostat
and could cause personal injury and/or property damage.

Thermostat installation and all components of the system
shall conform to Class 2 circuits per the NEC code.

Technical Data

Power

Working Environment

Range

Shell

Dimension

Connection Interface

Wireless Frequency 

Communication baud rate

Wireless Channels

Communication Distance

AC24V, 50/60Hz

30°F~99°F

0~90%RH(non-condensing)

Fire Retardant PC ABS

4.55x3.85x1.78 in (HxWxD)

Each terminal is capable of accepting

2 x 18 AWG solid copper wires.

433MHz

2.4 kbps

1~10 Channels

Beeline distance 200ft in the field. (The

distance will shorten through walls and floors)

4

.5

5

1.78”

3.85”

C

R

E

/W

1

W

2

Y

2

G

O

B

N

C

Y

1

Copyright © 2009 EWC Controls All Rights Reserved

To conserve power, the EWT-3900 leaves the 
factory in Standby Mode.  When removed from 
the box, “PE” will be displayed on the LCD to 
indicate Standby Mode. When you are ready to 
use the thermostat, press and hold the           
round center button for five seconds to exit 
Standby Mode.

 

Summary of Contents for EWT-3900 Ultra-Zone

Page 1: ...Thermostat can be programmed between 45 F and 95 F l Backlit display l Air Filter Replacement Monitor The Model EWT 3900 Wireless Thermostat is Linked to the Receiver at the factory Simply power up the Receiver then program and operate the Thermostat AUTO FAN SYSTEM HEAT PM 1 MON Room DAY TIME PROG PROG DAY FAN HOLD RUN MODE Reviews filter usage in hours and minutes and also activates standby mode...

Page 2: ...han is subject to freezing and or condensation EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 E Mail info ewccontrols com 2 CAUTION To prevent electrical shock and or equipment damage disconnect electric power to HVAC system at main fuse or circuit breaker box until installation is complete WARNING Do not use circuits exceeding specified voltage Higher voltage w...

Page 3: ...lower Fan Energized on call for Heat and Cool Energized in Cool Mode Energized in Heat Mode Heat Pump 2 2nd Stage Compressor THERMOSTAT TERMINALS CONVENTIONAL SYSTEM C R E W1 W2 Y1 Y2 G O B Single Stage 24 Volt Common 24 Volt hot Heat Mode 1st stage No Output Cool mode 1st stage compressor No output Blower Fan Energized on call for Cool and Heat if HE was selected No Output No Output Multistage 2n...

Page 4: ... hold the key for five seconds to enter the configuration menu The display will show the first item in the configuration menu The configuration menu table shows the configuration options and an explanation of each option Press the key to step to the next menu item To exit the menu and return to program operation press key If no keys are pressed within fifteen seconds the thermostat will revert bac...

Page 5: ...et point and the Cool set point can not be set lower than the Heat set point 1 Put Thermostat into RUN MODE in either heat or cool 2 Select program mode either 5 2 day or 7 individual days by pressing key until desired program is selected 3 Press key and in the program window will appear the hour flashing Use the or keys to set the hour Note AM or PM 4 Press key again to change to the minute posit...

Page 6: ...he heating system should stop operating Copyright 2009 EWC Controls All Rights Reserved FAN FAN MODE Heating System Heatpump Application Only 1 Press the key until HEAT shows on the LCD display 2 Press key to adjust thermostat setting to 2 F 1 C above room temperature The heating system should begin to operate The display should show STG1 However if the set point temperature display begins to flas...

Page 7: ...revent unauthorized changes from being made To lock or unlock the keyboard press and hold the button for 3 seconds The keyboard is locked when LOCK appears on the display Anytime a key is pressed LOCK will appear on the screen for one second To exit Lock mode press and hold the key for 3 seconds Filter Monitor Your thermostat also keeps a record of the number of days your filter has been in use To...

Page 8: ...L EWT BC USB CABLE INCLUDED WITH EWT 3900 MODEL EWT 3900 The Model EWT BC is an optional wall charger for the Model EWT 3900 Wireless Thermostat TO USE Attach the USB Cable Provided with the EWT 3900 to the Thermostat and the Charger Then plug the charger into the wall Allow the thermostat to charge for at least 12 hours during the first three charging cycles in order to condition the battery prop...

Page 9: ...adio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits If necessary the user should consult the dealer or an experienced radio television technician for additional suggestions The user or instal...

Page 10: ...This page is left blank intentionally EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 E Mail info ewccontrols com Copyright 2009 EWC Controls All Rights Reserved ...

Reviews: