WT.050.590.002.UA.IM.0614
45
SFC ANALYZER / CONTROLLER
EVOQUA
W3T109634
Switch settings of DIP switch S4:
S4-A
1
S4-B
2
S4-C
3
Potentiometer 1K
Off
Off
On
Potentiometer 5K
Off
Off
Off
0/4-20mA
On
On
Off
0-1 V
On
On
Off
3.8
Digital Inputs
Two digital inputs are integrated in the IC board of the SFC-SC. These are
provided for connecting voltage-free contacts (< 100 Ohm) and are supplied
internally with 12 V. Various processing and switching functions can be trig-
gered using the digital inputs.
WARNING: NO VOlTAGE MAy BE ApplIED TO ThE DIGITAl INpUT TER-
MINAlS!
3.9
Unit Configuration
The SFC-SC gives the option of saving all unit settings as a configuration.
Unit settings include all parameters that can be set in the menu, such as
the dosing factor, control output, etc. A maximum of two configurations
can be saved in the internal memory SFC-SC.
If configurations are saved in the internal memory as Job 1 and Job 2, they
can be restored when required as the current unit settings. The previous unit
settings are deleted in the process. It is possible to switch between Job 1 and
Job 2 via digital input 1 or 2.
When "Job 2" is selected, a signal on the digital input causes configuration 2 to
be loaded, and the SFC-SC continues to operate with the unit settings of Job 2.
If the signal on the digital input is deactivated, then configuration 1 is loaded
again and the SFC-SC continues to operate with the unit settings of Job 1.
The digital input needs to be assigned to Job 2 in both configurations.
!
Summary of Contents for Wallace & Tiernan SFC-SC
Page 11: ...WT 050 590 002 UA IM 0614 SFC ANALYZER CONTROLLER EVOQUA W3T109634...
Page 12: ......
Page 19: ......
Page 47: ...WT 050 590 002 UA IM 0614 34 SFC ANALYZER CONTROLLER EVOQUA W3T109634...
Page 48: ......
Page 60: ...WT 050 590 002 UA IM 0614 46 SFC ANALYZER CONTROLLER EVOQUA W3T109634...
Page 61: ......
Page 77: ...WT 050 590 002 UA IM 0614 62 SFC ANALYZER CONTROLLER EVOQUA W3T109634...
Page 78: ......
Page 81: ......