68
WT.050.590.002.DM.IM.1218
Installation
SFC fieldbus module retrofit set
4.
E
n
g
li
s
h
4.8
Commissioning
4.8.1
Configuring the fieldbus module
As soon as the SFC has detected the fieldbus module the gateway
configuration menu is accessible.
Select MENU -> Inputs/Outputs -> Fieldbus to configure the
settings for the various bus systems.
Profibus DP
In Profibus DP the Profibus address can be set to any value
between 0 - 126.
Profinet
In Profinet the device name needs to be configured. The maximum
length of the device name is 16 characters.
Modbus TCP
In Modbus TCP the TCP/IP settings need to be configured.
Please note
Whenever the fieldbus settings are changed the fieldbus module
restarts.