EVO/
™ECM-Modbus RTU
Series 2
Page 22
Application Guide
©2020 All Rights Reserved
Evolution Controls Inc.
San Diego, CA USA
Read Multiple Coil Registers Command (01)
Address Command
Code
Starting Register
Number of Registers
Error Check
1-247
01
00
00
00
34
CRC-16
•
Unit, group 1, or group 2
address
must be 1-247 (one byte)
•
The
command code
is 01 (one byte).
•
The
starting register
is two bytes long. The value must be 00 00 when addressing an EVO/ECM-
Modbus RTU.
•
The
number of registers
is two bytes in length. The high byte is always 00. The low byte is
always 34 reading all 34 coil registers.
Reply to Modbus Master
Byte
Data
Address
Command
Code
Count
Coil 1-8
Coil 9-16 Coil 17-24 Coil 25-32 Coil 33-40
Error
Check
1-247
01
5
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO CRC-16
•
The
byte count
is 5 bytes. The more significant bits contain the higher coil variables. Coil 35 to
40 are not used.