evoheat Solace 1.25 Installation & Operation Manual Download Page 16

Press the key of "UP" or "Down" to check that if  there are more failure codes.
You can find solutions to the problems according to the codes.

15

Solution

Malfunction

Code

P1

P2

P3

P5

P6

P7

P8

E0

Reason

Solution to failure P1/P2/P3
1. If P1/P2/P3 appears together with other failures, please solve the others first.
2. If there is no other failures of P3~E0, and P1 & P2 still exist, please disconnect the power to 
the unit and connect again after 1 hour.
3. If only P3 exists, please keep the fan running for 30min. If P3 still exist after the running,
please disconnect the power to the unit and connect again after 1 hour.

Note: Please contact with 

when failures can not be solved. 

Technical Service Assistance 

6. Maintenance

6.2 Troubleshootings

14

High pressure protection

Condenser outlet
 temp. overhigh

Evaporator outlet temp. 
sensor failure

Humidity sensor failure

Motor feedback 
signal failure

Evaporator inlet temp. 
sensor failure

Condenser outlet temp. 
sensor failure

High pressure protection 
has appeared 3 times in 
30mins.

High pressure protection 

is too frequently.

Condenser coil temp.

is too high

This temp. sensor is

 broken or in short circuit

The feedback wiring is in 
bad connection. 
Or  fan motor is damaged. 

This temp. sensor is 

broken or in short circuit

This temp. sensor is 

broken or in short circuit

This humidity sensor is 

broken or in short circuit

Discharge pressure 

is too high 

1.Check the feedback
    wiring of fan motor.
2.Or replace the fan 
     motor.

Check or replace 

this temp. sensor

Check the below 

solutions to failure 

P1/P2/P3

Check or replace 

this temp. sensor

Check or replace 

this temp. sensor

Check or replace this

 humidity sensor

Fig.14

Fig.15

6. Maintenance

4

 

Set the filter net and the air return grille to the original place. (Fig.14)

5

Clean  up the unit outer with soft and damp rag

Fig.15

 To protect the paint-coat of the 

unit, please don

t  use rough sponge or  corrosive detergent to do these.

 Warning£Cut off power supply before cleaning or maintaining the unit.

Summary of Contents for Solace 1.25

Page 1: ...SOLACE SERIES SWIMMING POOL DEHUMIDIFIER Installation Operation Manual...

Page 2: ...nciple 3 5 Product Features 3 6 Hygrostat Control 4 Installation 5 Usage 5 1 Instruction for Operation Panel 5 2 Operation Instruction 6 Maintenance 7 1 PCB I O Port 7 2 Wiring Diagram Safety Precauti...

Page 3: ...truction must be kept carefully and must always accompany the appliance If it is lost or damaged please contact the local technical service center 1 1 Fail to comply with these recommendations will in...

Page 4: ...ated Do not put fingers or others into the fan or evaporator of the unit otherwise harm may be occurred OPERATION PROHIBITION SHUT OFF THE POWER When the unit needs to be moved or installed again plea...

Page 5: ...agent or similarly qualified persons in order to avoid a hazard 7 It is forbidden to poke objects or anything else through the inlet or outlet grills 8 It is forbidden to dispose of or leave in the re...

Page 6: ...20 240V 50Hz 10 36 See nameplate package label R410A 600g See 3 3 Operation Pressure Side High Operation Pressure Side Low Condensation Pipe Diameter 4 4 2 1 16 4 4 2 1 16 Model Rated Capaclty Air Vol...

Page 7: ...mance Curve Solace 2 5 40 35 30 25 20 15 10 5 0 0 0 5 1 0 1 5 2 0 l h C 0 40 RH 2 5 60 RH 80 RH 40 35 30 25 20 15 10 5 0 0 0 5 1 0 1 5 2 0 l h C 0 40 RH 3 5 60 RH 80 RH 2 5 3 0 40 35 30 25 20 15 10 5...

Page 8: ...coil of the refrigeration device condenses the water which is removed then the air is reheated by the hot coil This process works most effectively with higher ambient temperatures with a high dew poin...

Page 9: ...e perfectly combined with your pool house 3 5 4 Newly design controller With simple operating display the newly developed controller makes the unit operation easier and more user friendly 3 6 1 The de...

Page 10: ...as filter cleaning 4 2 Positioning 4 2 1 Avoid installing the unit in proximity to positions subject to exposure to direct sunlight sources of heat in places with oil fumes places subject to high freq...

Page 11: ...6 Attention If the condensation water discharges directly into a container the condensate outlet should above the container to avoid immersing in the container Select a suitable size hose to connect t...

Page 12: ...the target setting value DOWN 10 RH Defrosting Dehumidifying Press this button once to check the target setting value of relative humidity Press it again can decrease the target setting value Tips Wh...

Page 13: ...Set the target value of relative humidity Press or to check the target relative humidity 11 RH RH Actual relative humidity The selected mode RH RH Press or again to change the target relative humidit...

Page 14: ...ction Operation panel will display the failure codes when the unit gets some malfunctions Please refer to page15 to check the meaning of failure codes RH 5 2 3 Dehumidifying mode When the unit is in d...

Page 15: ...an up the unit every six months Please take the following steps to clean up the strainer regularly 1 Pull out the grill A from the upside of it Fig 8 2 After that pull out the grill Fig 9 then lift th...

Page 16: ...urn grille to the original place Fig 14 5 Clean up the unit outer with soft and damp rag Fig 15 To protect the paint coat of the unit please don t use rough sponge or corrosive detergent to do these W...

Page 17: ...roubleshootings High pressure protection Condenser outlet temp overhigh Evaporator outlet temp sensor failure Humidity sensor failure Motor feedback signal failure Evaporator inlet temp sensor failure...

Page 18: ...HUMI01 HUMI02 CN7 EEV PROG1 L N1 N_Comp N_Valve L_Comp Meaning To operation panel Reserved To fan motor DC To evaporator inlet outlet temp sensor To condenser outlet temp sensor To the build in hygro...

Page 19: ...S TEMP2 HUMI01 HUMI02 TEMP 1 EEV CN1 FM PACC1001 t t 5K CdOT t 5K C1 Operation Panel TO POWER SUPPLY HPS CN7 CdOT Condenser OutletTemperature SS Sensitive Switch EvOT Evaporator Outlet Temperature EvI...

Page 20: ...Code 20121115 0004...

Reviews: