evoheat CS-i Series Installation & Operation Manual Download Page 7

 

 

EvoHeat CS-i Commercial Inverter Series Heat Pump 

4.2 Location Recommendations 

Installation and service must be performed by a qualified installer. 

Evo recommend the heat pump should be installed in an outdoor location with appropriate ventilation. Installing the 

heater indoors without adequate ventilation, or in a poorly ventilated enclosed space, will result in very poor 

performance and can, in extreme cases, damage the heater. Ensure the heater is installed in a well-ventilated area 

with plenty of fresh air. 

Evo recommend the heat pump should ONLY be installed in a location with appropriate ventilation. 

If installing the heater on an existing pump/filtration system, the heater must be installed AFTER the filter and 

BEFORE the chlorinator/sanitizer. 

The heat pump should be installed on a flat level surface as close as possible to the pool. 

The Evo pool heat pump should be installed with a minimum clearance of at least 3.5m to the water’s edge. 

Furthermore, EvoHeat recommend installing the heat pump no greater than 7.5 meters away from the water’s edge 

due to heat loss from the piping. 

A rough estimate of heat loss over a 30m pipe run can be as high as 600 Watts per hour per 5 degrees of 

temperature difference between the air/ground and the pool water. These losses need to be taken into account over 

long distances and piping may need to be insulated to reduce heat leakage. 

The heat pump should be installed a maximum of 5m below the water level of the pool/spa. If further than 5M 

please discuss with your EvoHeat specialist for the best advice. 

Make sure the heat pump is not located where large amounts of water may run-off from a roof into the unit. Sharp 

sloping roofs without gutters will allow excessive amounts of rainwater mixed with debris from the roof to be forced 

through the unit. A water deflector may be needed to protect the heat pump. 

4.3 Airflow Clearances 

The heat pump unit needs continuous fresh air 

whilst running. The heater draws up to 47000 m3/h 

ambient air through the sides and discharges 

through the top fan cowl. 

Installing the heater indoors or in an enclosed 

space will result in very poor performance and can 

in extreme cases damage the heater. Ensure the 

heater is installed in a well-ventilated area with 

plenty of fresh air, a minimum gap between 

walls/fences etc of 1000mm on the sides and 

3500mm overhead clearance.  

When units of a similar height are placed side by 

side, EvoHeat recommend a 1500mm clearance between units. 

*Fan discharge distance can be reduced by adding a Plenum to alter the air flow direction. Contact EvoHeat or a 

HVAC specialist for further advice. If you do not have a location with these suggested clearances, please contact our 

EvoHeat Tech Support Specialist to discuss appropriate installation locations. 

Leave sufficient space for unobstructed airflow into and out of the heater. Do not locate the heater in an enclosed 

area, or the discharged cold air will recirculate into the unit and consequently lower the heating efficiency as well as 

possible icing up. 

 

Summary of Contents for CS-i Series

Page 1: ......

Page 2: ...Start up Shut Down ___________________________________________________________________ 9 5 2 2 Switching Modes Setting the Target Temperature ___________________________________________ 9 5 2 3 Clock...

Page 3: ...130 Heat output at 27 C air 26 C water kW 65 130 Heat output at 15 C air 26 C water kW 50 100 Cooling output at 55 C air 35 C water kW 15 54 Cooling output at 45 C air 26 C water kW 30 73 C O P AT 27...

Page 4: ...oHeat CS i Commercial Inverter Series Heat Pump 2 Unit Dimensions Evo CS i 65 unit mm Evo CS i 130 A L B W C H Water inlet outlet CS i 65 1750mm 830mm 1750mm 50 CS i 130 2260mm 1160mm 2127mm 100mm fla...

Page 5: ...oad protection system After a previous stoppage the unit will not start for at least 3 minutes For unit cleaning or maintenance switch off and disconnect the power of the unit Do not install the unit...

Page 6: ...on the front panel of the unit The gauge should be showing a pressure of approx 10 20 on the outside red band any less than this figure means there may be a leak in the refrigerant system and you shou...

Page 7: ...nstalled a maximum of 5m below the water level of the pool spa If further than 5M please discuss with your EvoHeat specialist for the best advice Make sure the heat pump is not located where large amo...

Page 8: ...in the air condenses on the fins of the evaporator During times of high humidity the condensate may be several litres per hour This may give the impression that the heater is leaking however this is a...

Page 9: ...he unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger After installation is completed follow the steps below 1 Turn on your filter pump Check fo...

Page 10: ...perature interface 7 Temperature Curve Click to view the temperature and power curve 8 Water Inlet Temperature Press to enter mode setting and the target temperature interface 9 LOCK Click to lock the...

Page 11: ...nction 1 Timing Start Button Start Green End Grey Click this button to start or end the timing start setting function 2 Timing On Setting Click to set the start time of the timer 3 Timing End Button O...

Page 12: ...check the failure record the main interface will display a static The failure record is in reverse order according to the time of occurrence Press the clean key to delete all fault records 5 2 6 Colou...

Page 13: ...eaners to ensure proper water flow Is the current pool spa water temperature higher than the set temperature on the controller If so the unit will not operate until the pool spa water temperature fall...

Page 14: ...If the water has chlorine it is a water leak and you need to contact EvoHeat tech support on 1300 859 933 Or Turn the heater off and run the water pump continuously for a period of 2 4 hours If the wa...

Page 15: ...rcuit Flow Switch Prot E03 No water little water in water system Check the pipe water flow and water pump Waterway Anti freezing Prot E05 Water temp or ambient temp is too low Inlet and outlet temp to...

Page 16: ...eck the input voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication...

Page 17: ...101 123A 2 x 35mm2 35mm2 160A 30mA less than 0 1 sec 123 148A 2 x 50mm2 50mm2 225A 30mA less than 0 1 sec 148 186A 2 x 70mm2 70mm2 250A 30mA less than 0 1 sec 186 224A 2 x 95mm2 95mm2 280A 30mA less t...

Page 18: ...17 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 Wiring Diagrams 7 3 1 CS i 65...

Page 19: ...18 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 2 CS i 130...

Page 20: ...rature input 13 AI DI06 Water input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch...

Page 21: ...time 8 1 Energy Saving Tips If your pool water is allowed to cool significantly it may take several days to return to the desired swimming temperature For weekend use it is more economical to maintai...

Page 22: ...y handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b prov...

Reviews: