evoheat CS-i Series Installation & Operation Manual Download Page 16

 

 

15 

EvoHeat CS-i Commercial Inverter Series Heat Pump 

Frequency Conversion Board Fault Table 

Protect/fault

 

Fault 

display

 

Reason

 

Elimination methods

 

 

Drv1 MOP alarm 

F01

 

MOP drive alarm

 

Recovery after the 150s

 

 

Inverter offline 

F02

 

Frequency conversion board and 

main board communication failure

 

Check the communication connection

 

 

IPM protection 

F03

 

IPM modular protection

 

Recovery after the 150s

 

 

Comp. Driver Failure 

F04

 

Lack of phase, step or drive 

hardware damage

 

Check the measuring voltage check 

frequency conversion board hardware

 

 

DC Fan Fault 

F05

 

Motor current feedback open circuit 

or short circuit

 

Check whether current return wires 

connected motor

 

 

IPM Overcurrent 

F06

 

IPM Input current is large

 

Check and adjust the current measurement

 

 

Inv. DC Overvoltage 

F07

 

DC bus voltage>Dc bus over-voltage 

protection value

 

Check the input voltage measurement

 

 

Inv. DC Less voltage 

F08

 

DC bus voltage<Dc bus over-voltage 

protection value

 

Check the input voltage measurement

 

 

Inv. Input Less volt. 

F09

 

The input voltage is low, causing 

the input current is high

 

Check the input voltage measurement

 

 

Inv. Input Overvolt. 

F10

 

The input voltage is too high, 

more than outage protection 

current RMS

 

Check the input voltage measurement

 

 

Inv. Sampling Volt. 

F11

 

The input voltage sampling fault

 

Check and adjust the current measurement

 

 

Comm. Err DSP-PFC 

F12

 

DSP and PFC connect fault

 

Check the communication connection

 

 

Input Over Cur. 

F26

 

The equipment load is too large

 

 

 

PFC fault 

F27

 

The PFC circuit protection

 

Check the PFC switch tube short circuit or 

not

 

IPM Overheating 

F15

 

The IPM module is overheat

 

Check and adjust the current measurement

 

Weak Magnetic Warn 

F16

 

Compressor magnetic force is not 

enough

 

 

Inv. Input Out Phase 

F17

 

The input voltage lost phase

 

Check and measure the voltage adjustment

 

IPM Sampling Cur. 

F18

 

IPM sampling electricity is fault

 

Check and adjust the current measurement

 

Inv. Temp. Probe Fail 

F19

 

Sensor is short circuit or open circuit

 

Inspect and replace the sensor

 

Inverter Overheating 

F20

 

 

The transducer is overheat

 

Check and adjust the current measurement

 

Inv. Overheating Warn 

F22

 

Transducer temperature is too high

 

Check and adjust the current measurement

 

Comp. Over Cur. Warn 

F23

 

 

Compressor electricity is large

 

The compressor over-current protection

 

Input Over Cur. Warn 

F24

 

 

Input current is too large

 

Check and adjust the current measurement

 

EEPROM Error Warn 

F25

 

MCU error

 

Check whether the chip is damaged Replace 

the chip

 

V15V over/undervoltage 

fault 

F28 

The V15V is overload or 

undervoltage

 

Check the V15V input voltage in range 

13.5v~16.5v or not

 

 

 

 

 

Summary of Contents for CS-i Series

Page 1: ......

Page 2: ...Start up Shut Down ___________________________________________________________________ 9 5 2 2 Switching Modes Setting the Target Temperature ___________________________________________ 9 5 2 3 Clock...

Page 3: ...130 Heat output at 27 C air 26 C water kW 65 130 Heat output at 15 C air 26 C water kW 50 100 Cooling output at 55 C air 35 C water kW 15 54 Cooling output at 45 C air 26 C water kW 30 73 C O P AT 27...

Page 4: ...oHeat CS i Commercial Inverter Series Heat Pump 2 Unit Dimensions Evo CS i 65 unit mm Evo CS i 130 A L B W C H Water inlet outlet CS i 65 1750mm 830mm 1750mm 50 CS i 130 2260mm 1160mm 2127mm 100mm fla...

Page 5: ...oad protection system After a previous stoppage the unit will not start for at least 3 minutes For unit cleaning or maintenance switch off and disconnect the power of the unit Do not install the unit...

Page 6: ...on the front panel of the unit The gauge should be showing a pressure of approx 10 20 on the outside red band any less than this figure means there may be a leak in the refrigerant system and you shou...

Page 7: ...nstalled a maximum of 5m below the water level of the pool spa If further than 5M please discuss with your EvoHeat specialist for the best advice Make sure the heat pump is not located where large amo...

Page 8: ...in the air condenses on the fins of the evaporator During times of high humidity the condensate may be several litres per hour This may give the impression that the heater is leaking however this is a...

Page 9: ...he unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger After installation is completed follow the steps below 1 Turn on your filter pump Check fo...

Page 10: ...perature interface 7 Temperature Curve Click to view the temperature and power curve 8 Water Inlet Temperature Press to enter mode setting and the target temperature interface 9 LOCK Click to lock the...

Page 11: ...nction 1 Timing Start Button Start Green End Grey Click this button to start or end the timing start setting function 2 Timing On Setting Click to set the start time of the timer 3 Timing End Button O...

Page 12: ...check the failure record the main interface will display a static The failure record is in reverse order according to the time of occurrence Press the clean key to delete all fault records 5 2 6 Colou...

Page 13: ...eaners to ensure proper water flow Is the current pool spa water temperature higher than the set temperature on the controller If so the unit will not operate until the pool spa water temperature fall...

Page 14: ...If the water has chlorine it is a water leak and you need to contact EvoHeat tech support on 1300 859 933 Or Turn the heater off and run the water pump continuously for a period of 2 4 hours If the wa...

Page 15: ...rcuit Flow Switch Prot E03 No water little water in water system Check the pipe water flow and water pump Waterway Anti freezing Prot E05 Water temp or ambient temp is too low Inlet and outlet temp to...

Page 16: ...eck the input voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication...

Page 17: ...101 123A 2 x 35mm2 35mm2 160A 30mA less than 0 1 sec 123 148A 2 x 50mm2 50mm2 225A 30mA less than 0 1 sec 148 186A 2 x 70mm2 70mm2 250A 30mA less than 0 1 sec 186 224A 2 x 95mm2 95mm2 280A 30mA less t...

Page 18: ...17 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 Wiring Diagrams 7 3 1 CS i 65...

Page 19: ...18 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 2 CS i 130...

Page 20: ...rature input 13 AI DI06 Water input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch...

Page 21: ...time 8 1 Energy Saving Tips If your pool water is allowed to cool significantly it may take several days to return to the desired swimming temperature For weekend use it is more economical to maintai...

Page 22: ...y handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b prov...

Reviews: