INSTALLATION
evo HE C -
Installation and Servicing
FLUE OUTLET
Notes.
1.
It is recommended that a support bracket is
fitted for every 1 meter of extension pipe used
and a bracket should be used at every joint,
to ensure pipes are held at the correct angle.
If a slip joint coupling is to be used then a
bracket should be used to secure the collar.
2.
When extension ‘D’ packs are used the flue
duct MUST be inclined at 1.5 degrees to the
horizontal to allow condensate to drain back
into the boiler and out through the
condensate drain.
3.
If the telescopic ‘B’ pack, or horizontal flue
terminal (600 long) only are used, they may
be mounted horizontally. The 1.5 degrees is
taken care of by the inclination of the flue
within the air pipe.
4.
If the boiler is to be installed with upward
piping routed behind the boiler then the
optional stand-off kit should be used. Care
must be taken when cutting the ducts and
marking the wall to suit this condition.
5.
Only use water as a lubricant during
assembly. Do not use mineral based oils.
Total Flue length dimension
Flue
(measuring from CL of turret to outside wall)
Rear flue
Side flue
Extra packs
Boiler
dim. X+160
dim. L+195
required
Size
Up to 595 mm
Up to 595 mm
none
C22/24,30 & 35
Up to 1545 mm Up to 1545 mm
Pack D - 1 off
C22/24,30 & 35
Up to 2495 mm Up to 2495 mm
Pack D - 2 off
C22/24,30 & 35
Up to 3445 mm Up to 3445 mm
Pack D - 3 off C22/24,30 & 35*
Up to 4395 mm Up to 4395 mm
Pack D - 4 off
C22/24 & 30
Up to 5345 mm Up to 5345 mm
Pack D - 5 off
C22/24 & 30
Up to 6000 mm Up to 6000 mm
Pack D - 6 off
C22/24 & 30
*evo HE C22/35 is capable of 3m flue only
12A
CONT’D DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
1
nm
8760
13 FLUE ASSEMBLY - Exploded View
An optional flue duct extension kit is
required for wall thicknesses greater
than :
Side
395mm
Rear
435mm
Rear flue arrangement shown
LEGEND
1.
Duct assembly.
2.
Flue turret.
3.
Turret gasket.
4.
M5 x 10 pozi screw.
5.
Turret clamp.
The flue terminal MUST be
fitted with the ‘TOP’
uppermost to allow the
correct fit and use of the
plume management system.
TOP