E2608-Cl2
Rev 05.05.2021
RE1
2 – gas concentration
9 – control by Modbus control,
state set in MHR / 40214
0x00D4 212 / 40213 RW
Parameter tied to relay
RE2
0 – none
2 – gas concentration
9- – control by Modbus control,
state set in MHR / 40215
2
0x00D5 213 / 40214 RW
Forced state for relay
RE1***
0 –off, 1 – on
0
0x00D6 214/ 40215 RW
Forced state for relay
RE2***
0 – off, 1 – on
0
0x00D7 215 / 40216 RW
Switching delay for relay
RE1
0...1000 (s)
0
0x00D8 216 / 40217 RW
Switching delay for relay
RE2
0...1000 (s)
0
0x00D9 217 / 40218 RW
Minimal on/off time for
relay RE1
0...1000 (s)
0
0x00DA 218 / 40219 RW
Minimal on/off time for
relay RE2
0...1000 (s)
0
Address Reg / MHR RW Description
Supported values (dec)
Default
0x00DB
219 /
40220
RW
Control logic for relay RE1
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within
the range
4 – relay on for the values
out of the range
0
0x00DC
220 /
40221
RW
Control logic for relay RE2
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within
the range
4 – relay on for the values
out of the range
0
17