background image

Program Setting 

The above program time and temperature can be modified.   
 
To adjust Heat/Cool program settings: 

1.

 

In Heat/Cool Mode, press SET button to enter Setting Menu. 

2.

 

Press NEXT button to display PROG.   

3.

 

Press ENT button to enter program setting: “ON”/”OFF”. 

4.

 

Press UP or DOWN button to select program on / program off. 

5.

 

Make sure “On” is selected, press NEXT button to select the item 
that you want to change (Weekday/Weekend, Four Zones, 
Hour, Minute or Setting Temperature). 

6.

 

Press UP or DOWN button to adjust the item. 

7.

 

Press MODE button to return to Weekday/Weekend program 

8.

 

Press MODE button again, to confirm the setting and return to 
Setting Menu. 

9.

 

*** Press NEXT button to return to Normal Display Mode. 

 

Temporary Override 

When Program is On, this thermostat controls the output according 
to the program.   
 
If you want to override the programmed temperature temporarily: 
1.

 

Press UP or DOWN button to adjust Heat / Cool setting 

temperature setpoint with 

  displayed. 

2.

 

In Heat Mode, only Heat setting temperature can be adjusted. 

3.

 

In Cool Mode, only Cool setting temperature can be adjusted. 

4.

 

The Heat / Cool setting temperature will be confirmed and the 
thermostat will return to Normal Display Mode, if no key is 
pressed for 10 sec. 

 
Temporary Override Mode will last until the next programmed time 
(zone) begins. At that time, the Heat / Cool setting temperature will 

follow the programmed setting temperature and 

  will 

disappear. Or 

  can be stopped manually by pressing 

MODE key. 
 

Program Off 

When Program is Off, this thermostat controls the output according 
to a single setpoint like a simple setback thermostat. To set the unit 
to be Program Off, follow the above “Program Setting” to select 
Program Off. When this thermostat is Program Off, the Program 
Mode will be disabled and the time zone icons will disappear in 
Normal Display Mode. 
 

To adjust the setpoint at Program Off: 
1.

 

Press UP or DOWN button to adjust the Heat / Cool setting 

temperature. The icon 

  will NOT be shown in Program 

Off. 

2.

 

In Heat Mode, only Heat setting temperature can be adjusted. 

3.

 

In Cool Mode, only Cool setting temperature can be adjusted. 

4.

 

*** The Heat / Cool setting temperature will be confirmed.   

 

Fan Operation 

If FAN ON is selected, fan runs continuously. 
If FAN AUTO is selected, fan runs only when the Heating or Cooling 
system is on. Fan will be turned off 2 minutes after the Heating / 
Cooling system is off. 
 
 

Fan Mode setting: 
1.

 

Press SET button to enter Setting Menu. 

2.

 

Press NEXT button to display FAN and press ENT button. 

3.

 

Press UP or DOWN button to select FAN ON / FAN AUTO. 

4.

 

Press MODE button to confirm the setting and return to Setting 
Menu. 

5.

 

*** Press NEXT button to resume to Normal display mode 

 

Advanced Setting 

Advanced Setting

 

contains Function Setting Selection, Temperature 

Calibration and Room Temperature Display. 
 

Function Setting Selection 

 
 
 
 
 
 
 
 
 
1.

 

Press and hold SET and DOWN buttons for 2 seconds to enter 
Advanced Setting Mode. 

2.

 

The left letters represent Function Type; the right letters represent 
the settings. 

3.

 

Press UP or DOWN button to adjust the setting. 

4.

 

*** Press NEXT button to select Function Type or to return to Normal 
Display Mode at the end of Function Setting selection. 

 
Table of the Function Setting Selection 

Function Type 

Description 

LCD 
Display 

Setting 

12 (default) 

12hr/24hr 
Selection 

hr 

24 
°C   

Temperature 
Display Unit 

dE 

°F (default) 
05 (+/- 0.5

C ) 

10 (+/- 1.0

C ) 

10 (+/- 1

F) (default) 

Temperature 
Control Span 

SP 

20 (+/- 2

F) 

E (Electrical Heat) (default) 

Fan Control 

FC 

O (Gas/Oil Heat) 
S (10 seconds) (default) 

Heater 
Minimum-Off 
Delay 

dL 

L (4 minutes off time)   

 
Temperature Control Span   
It controls how much the room temperature can be deviated from the 
setpoint. A smaller degree will result in a more accurate control. A 
larger degree will result in less on/off cycling and it usually saves more 
energy. 
 
Fan Control   
It should be set according to the type of Heating system used. Select 
“E” for Electric Heat, fan will be On when Heat is On. Select “O” for 
Gas Heating or Oil Heating, fan will NOT be on when Heat is On. 
 
Heater Minimum Off Delay   
It should be set according to the heater type. Select “L” if compressor 

is used for heating. Select “S” when a compressor is not used. 
 

Temperature Calibration 

This thermostat is calibrated at factory and calibration is 
generally not required. However, in the event that a deviation is 
found,   
 
1.

 

In Normal Display Mode, press and hold UP and DOWN 
buttons for 5 seconds to change the temperature calibration 
display and the current temperature will flash,   

2.

 

Press UP and DOWN button to calibrate the temperature. The 
maximum range to be adjusted is +/- 3.0°C or +/- 6°F, in step 
of 0.5°C / 1°F. 

3.

 

***Press MODE key to confirm the

 

setting and return to Normal 

Display Mode. 

 

Room Temperature Display (for Checking by Technician) 

 
 
 
 
 
 
 
 
 
1.

 

In Normal Display Mode, press and hold MODE and SET 

buttons for 5 seconds to display the room temperature in 
small display. 

2.

 

*** Press MODE key to return to Normal Display Mode. 

 

Replaceable Batteries   

When 

  appears on the display, replace the batteries 

promptly with 2 fresh AAA alkaline batteries. Batteries should be 
installed with proper polarity. Do not mix old and new batteries. 
 

 

Specification 

1.

 

Temperature Measurement:    0 - 40

C / 32 - 99

2.

 

Accuracy: 

 

 

±0.5

C / 1°F 

3.

 

Resolution: 

 

   

0.5

C /1°F 

4.

 

Power Supply:             

   

24Vac or 2 x AAA Alkaline 

 

 

 

 

 

Batteries 

5.

 

Rating: 

 

 

   

24Vac 50/ 60Hz 1A Max 

6.

 

Relay Contact Voltage: 

24Vac Max. 50/60 Hz 

7.

 

Relay Contact Current:    

1A Max. (Inductive) 

8.

 

Sensing Element:     

 

NTC Thermistor (with External 

 

 

 

 

 

Cable 36” ) 

9.

 

Heat/Cool Setting: 

   

16 - 35

C / 60 - 95

10.

 

Operating Temperature: 

0 - 50°C / 32 - 122°F 

11.

 

Storage Temperature:     

-5 - 50°C / 23 -122°F 

 
Remarks: 
*** The operation will return to Normal Display Mode if no key is 
pressed for 10 sec. 
 

 

Evergreen Products, LLC 

www.egreenproducts.com 

[email protected] 

<Down> Key   

 

Function 
Type   
 

<NEXT> Key   

Setting 

 

<Up> Key 

Setpoint 

Room 
Temperature 

Reviews: