Instruction manual for the bypass system of the POWERLINE 33 60-140 kVA UPS units 

 

2016-01-18 05:42

 

Technical support

, tel.: +48 61 6500 400

 

www.ever.eu

 

SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER  

Follow  this  procedure  to  switch  the  isolated  mains-powered  network  (Fig.  1)  to  the 

UPS power: 

1.  Make sure that the UPS has been powered off on the logical level. 

2.  Turn on the switch fuse Fm on the UPS input line (also turn on Fb if the UPS has 

a separate BYPASS line option). 

3.  Wait  until  the  UPS  indicates  that  the  connected  receivers  are  powered  via  the 

internal bypass with the red LED 

– STANDBY mode. 

4.  Turn on the switch disconnector Qout on the UPS output line. 

5.  Turn off the switch fuse Fsb on the bypass line. 

6.  Turn off the switch disconnector Qsb on the bypass line. 

7.  Turn on the UPS. To do this, go in the interface to: Menu -> Control -> UPS ->On 

(the  UPS  will  be  powered  on  on  the  logical  level) 

–  red  LED  goes  off  MAINS 

mode.  

 

 

CAUTION! 

Once  the  procedure  for  restoring  the  UPS  power  has  been 

completed,  secure  the  disconnectors  and  fuses  on  the  external  bypass 

line from inadvertent switching on by unauthorised personnel. 

 

 

 

Summary of Contents for POWERLINE 60-33

Page 1: ......

Page 2: ...ical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 OPERATING THE EXTERNAL BYPASS SYSTEM 3 SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE 5 SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER 6 TECHNICAL FEATURES 7 TECHNICAL SPECIFICATIONS 7 NOTES 7 ...

Page 3: ...tion Manual of this UPS before attempting any switching operations CAUTION Only trained personnel may switch power to the external bypass system Switching operations carried out against this procedure may result in damage to the UPS CAUTION Read and understand the Instruction Manual for this UPS before attempting the switching operation OPERATING THE EXTERNAL BYPASS SYSTEM Figure 1 Installation di...

Page 4: ... wires Install the switch fuse Fb breaker Fspd1 and surge protector SPD1 only if the optional input BYPASS security The list of safeguards with the wire sizes for the UPS models is shown in a separate documentation Installation guidelines for the POWERLINE 33 60 140kVA UPS units This UPS has been designed for operation in TN systems Qsb Mechanically locked in the break position when receivers are ...

Page 5: ...do this go in the interface to Menu Control UPS Off the UPS will be powered off on the logical level 2 Wait until the UPS is turned off on the logical level and indicates that the connected receivers are powered via the internal bypass with the red LED STANDBY mode 3 Turn on the switch disconnector Qsb on the bypass line 4 Turn on the switch fuse Fsb on the bypass line 5 Turn off the switch discon...

Page 6: ...BYPASS line option 3 Wait until the UPS indicates that the connected receivers are powered via the internal bypass with the red LED STANDBY mode 4 Turn on the switch disconnector Qout on the UPS output line 5 Turn off the switch fuse Fsb on the bypass line 6 Turn off the switch disconnector Qsb on the bypass line 7 Turn on the UPS To do this go in the interface to Menu Control UPS On the UPS will ...

Page 7: ...echnical support tel 48 61 6500 400 2016 01 18 05 42 TECHNICAL FEATURES TECHNICAL SPECIFICATIONS PARAMETERS MODEL EXTERNAL BYPASS FOR POWERLINE 33 60 100kVA EXTERNAL BYPASS FOR POWERLINE 33 120 140kVA Dimensions height width depth 1050 x 660 x 270 mm 1250 x 660 x 270 mm Net weight 48 kg 60 kg NOTES ...

Reviews: