Ever Cool Ltd, Viglen House Business Centre, Alperton Lane, London HA0 1HD
Tel: 020 8601 7157 Fax: 020 8997 0395 Web: www.evercoolltd.co.uk E-Mail: [email protected]
Company Registration No: 6096265 Company VAT No: 809764984
SET 0 (ST-0)
SET 0 has four sublevels:
pb, ti, td
and
cy
.
pb
:
Proportional valve of process.
ti
:
Integral process time.
td
:
Process derived
cy
:
Process action cicle
SET 1 (ST-1)
SET 1 has two sublevels:
Db.cl
and
Crcl
.
Db.cl
:
Cooling on delay (factory set at 2).
Example:
Set temperature value: 80oC
Db.cl set at 2 will energise the cooling solenoid valve at 82oC.
Crcl
:
Cooling relative gain ( factory set at 0,4 )
If the cooling water is from one chiller you can change it to a 0,2.
to allow change datas press
and the first digit to be set will flash modify
it with
keys press
to confirm.
SET 2 (ST-2)
Internal adjustment, non accessible.
SET 3 (ST-3)
SET 3 has three sublevels :
AO.H, AO.L
and
AO.S
AO.H
High oulet tension limit 4-20mA
AO.L
Low oulet tension limit 4-20mA
AO.S
Sign oulet tension limit 4-20mA
Only for units working with
current loop
system.