A10 0 240 min
5
duration of a power cut such to cause the power cut alarm
to be memorised ( “
PF
” code)when the power is supplied
0 = the alarm will not be signalled
AA 0 240
s
5
duration of buzzer activation on conclusion of blast chilling
and deep freezing
A11
0,1
15,0
°C/°F (1)
2,0
parameters A1 and A4 differential
A13
0
1
- - - -
1
memorisation of the temperature-controlled blast chilling or
temperature-controlled deep freezing non concluded within
maximum duration alarm (“
tiME
”)
1 = yes
Par.
Min.
Max.
Unit
Default
Evaporator and condenser fan
F0
0
2
- - - -
1
evaporator fan activity during pre-cooling, blast chilling and
deep freezing
0 = off
1 = on; see also parameters F16 and F17
2 = parallel to the compressor; see also parameters F9
and F17
F1 -99.0 99.0 °C/°F
(1) -1.0
evaporator temperature above which the evaporator fan is
off during storage (only if parameter F2 is set at 3); see
also parameter XS8(10)
F2
0
3
- - - -
3
evaporator fan activity during storage
0 = off
1 = on
2 = parallel to the compressor; see also parameter F9
3 = on; see also parameter F1
F3 0 15 min
2
duration of evaporator fan standstill (the compressor can be
on during evaporator fan standstill, the defrosting output
will remain deactivated and the evaporator fan will remain
off)
XS8
0.1
15.0
°C/°F (1)
2.0
F1, F16 and F17 parameters differential
F9 0 240
s
0
evaporator fan switch-off delay from compressor switch off
(only if parameter F0 and/or parameter F2 are set at 2)