EVCO S.p.A. | EVJ254 | Instruction sheet ver. 1.0 | Code 104J254I103 | Page 3 of 4 | PT 13/18 

55 

 

d25 

 

 

enable  air  out  probe  for  defrost 

during evaporator probe alarm 

0  = no 

1  = yes 

 

56 

 

 

d26 

 

 

 

 

defrost 

interval 

during 

evaporator probe alarm 

 

0... 99 h 

0  = only manual 

if d25 = 1 

 

N.

 

PAR.

 

DEF.

 

ALARMS

 

MIN... MAX. 

57 

 

A0 

 

 

select 

value 

for 

high/low 

temperature alarms 

0  = regulation temperature 

1  = evaporator temperature 

58 

 

A1 

 

0.0 

 

threshold  for  low  temperature 

alarm 

-99... 99 °C/°F 

 

59 

 

 

A2 

 

 

 

 

low temperature alarm type 

 

 

0  = disabled 

1  = relative to setpoint 

2  = absolute 

60 

 

A4 

 

0.0 

 

threshold  for  high  temperature 

alarm 

-99... 99 °C/°F 

 

61 

 

 

A5 

 

 

 

 

high temperature alarm type 

 

 

0  = regulation temperature 

1  = evaporator temperature 

2  = auxiliary temperature 

62 

 

A6 

 

120 

 

high  temperature  alarm  delay 

after power-on 

0... 240 min 

 

63 

 

A7 

 

15 

 

high/low 

temperature 

alarms 

delay 

0... 240 min 

 

64 

 

A8 

 

15 

 

high  temperature  alarm  delay 

after defrost 

0... 240 min 

 

65 

 

A9 

 

15 

 

high  temperature  alarm  delay 

after door closing 

0... 240 min 

 

66 

 

A10 

 

10 

 

power  failure  duration  for  alarm 

recording 

0... 240 min 

 

67 

 

A11 

 

2.0 

 

high/low 

temperature 

alarms 

reset differential 

1... 15 °C/°F 

 

68 

 

 

 

 

A12 

 

 

 

 

 

 

 

 

power  failure  alarm  notification 

type (not available in EVJ254N7) 

 

 

 

0  = HACCP LED 

1  = HACCP LED + PF label + 

buzzer 

2  = HACCP  LED  +  PF  label  + 

buzzer (if duration > A10) 

 

 

N. 

PAR. 

DEF.  FANS 

MIN... MAX. 

69 

 

 

 

 

 

 

 

 

 

 

 

F0 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

evaporator  fan  mode  during 

normal operation 

 

 

 

 

 

 

 

 

 

 

0  = off 

1  = on 

2  = on if compressor on 

3  = thermoregulated 

(with 

regulation  temperature 

+ F1) 

4  = thermoregulated 

(with 

regulation  temperature 

+ F1) if compressor on 

5  = according to F6 

6  = thermoregulated (with F1) 

7  = thermoregulated 

(with 

F1) if compressor on 

70 

 

F1 

 

-4.0 

 

threshold  for  evaporator  fan 

operation 

-99... 99 °C/°F 

 

71 

 

F2 

 

 

evaporator  fan  mode  during 

defrost and dripping 

0  = off 

1  = on 

2  = according to F0 

72 

 

F3 

 

 

evaporator  fan  off  maximum 

time 

0... 15 min 

 

73 

 

F4 

 

30 

 

evaporator  fan  off  time  during 

energy saving 

0... 240 s x 10 

if F0 

 5 

74 

 

F5 

 

30 

 

evaporator  fan  on  time  during 

energy saving 

0... 240 s x 10 

if F0 

 5 

75 

 

 

 

F6 

 

 

 

 

 

 

high/low humidity operation 

 

 

 

0  = low  humidity  (with  F17 

and  F18  if  compressor 

off, on if compressor on) 

1  = high humifity (on) 

76 

 

 

F7 

 

 

5.0 

 

 

threshold  for  evaporator  fan  on 

after 

dripping 

(relative 

to 

setpoint) 

-99... 99 °C/°F 

se F7 

 

77 

 

F8 

 

2.0 

 

threshold  for  evaporator  fan 

operation differential 

1... 15 °C/°F 

 

78 

 

F9 

 

10 

 

evaporator  fan  off  delay  after 

compressor off 

0... 240 s 

if F0 = 2 or 5 

79 

 

 

 

 

 

 

 

 

F10 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condenser fan mode 

 

 

 

 

 

 

 

 

0  = thermoregulated (with F11) 

1  = thermoregulated 

(with 

F11)  if  compressor  off, 

on if compressor on 

2  = thermoregulated 

(with 

F11)  if  compressor  off, 

on  if  compressor  on,  off 

during 

defrost, 

pre-

dripping and dripping 

80 

 

F11 

 

15.0 

 

threshold for condenser fan on 

 

0... 99 °C/°F 

differential = 2 °C/4 °F 

81 

 

F12 

 

30 

 

condenser  fan  off  delay  after 

compressor off 

0... 240 s 

if P4 

≠ 1

 

82 

 

F17 

 

60 

 

evaporator  fan  off  time  with  low 

humidity 

0... 240 s 

 

83 

 

F18 

 

10 

 

evaporator  fan  on  time  with  low 

humidity 

0... 240 s 

 

 

N. 

PAR. 

DEF.  DIGITAL INPUTS 

MIN... MAX. 

84 

 

 

 

 

 

 

 

 

 

i0 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

door switch input function 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = compressor 

evaporator fan off 

2  = evaporator fan off 

3  = cabinet light on 

4  = compressor 

evaporator 

fan 

off, 

cabinet light on 

5  = evaporator  fan  off  + 

cabinet light on 

85 

 

i1 

 

 

door switch input activation 

 

0  = with contact closed 

1  = with contact open 

86 

 

i2 

 

30 

 

open door alarm delay 

 

-1... 120 min 

-1 = disabled 

87 

 

i3 

 

15 

 

regulation  inhibition  maximum 

time with door open 

-1... 120 min 

-1 = until the closing 

88 

 

 

i4 

 

 

 

 

enable 

open 

door 

alarm 

recording 

(not 

available 

in 

EVJ254N7) 

0  = no 

1  = yes 

if i2 

≠ 

-1 and after i2 

 

89 

 

 

 

 

 

 

 

 

i5 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

multi-purpose input function 

 

 

 

 

 

 

 

 

0  = disabled 

1  = energy saving 

2  = iA alarm 

3  = iSd alarm 

4  = button-operated load 1 on 

5  = button-operated load 2 on 

6  = device on/off 

7  = LP alarm 

8  = C1t alarm 

90 

 

i6 

 

 

multi-purpose input activation 

 

0  = with contact closed 

1  = with contact open 

91 

 

 

i7 

 

 

 

 

multi-purpose input alarm delay 

 

 

0... 120 min 

if i5 = 3 or 7, compressor on 

delay after alarm reset 

92 

 

 

i8 

 

 

 

 

number  of  multi-purpose  input 

activations  for  high  pressure 

alarm

 

0... 15 

0  = disabled 

if i5 = 3 

93 

 

i9 

 

240 

 

reset  counter  time  for  high 

pressure alarm

 

1... 999 min 

 

94 

 

 

 

i10 

 

 

 

 

 

 

door  closed  consecutive  time  for 

energy saving 

 

 

0... 999 min 

after  regulation  temperature 

< SP 

0  = disabled 

95 

 

i13 

 

180 

 

number  of  door  openings  for 

defrost 

0... 240 

0  = disabled 

96 

 

i14 

 

32 

 

door  open  consecutive  time  for 

defrost 

0... 240 min 

0  = disabled 

 

N. 

PAR. 

DEF.  DIGITAL OUTPUTS 

MIN... MAX. 

97 

 

 

 

 

 

 

 

 

 

 

 

 

u1c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay K1 configuration 

 

 

 

 

 

 

 

 

 

 

 

 

0  = compressor 

1  = evaporator fan 

2  = condenser fan 

3  = defrost 

4  = cabinet light 

5  = demisting 

6  = door heaters 

7  = heater for neutral zone 

8  = dripping heater 

9  = button-operated load 1 

10 = button-operated load 2 

11 = alarm 

12 = on/stand-by 

98 

 

 

 

 

 

 

 

 

 

 

 

 

u2c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay K2 configuration 

 

 

 

 

 

 

 

 

 

 

 

 

0  = compressor 

1  = evaporator fan 

2  = condenser fan 

3  = defrost 

4  = cabinet light 

5  = demisting 

6  = door heaters 

7  = heater for neutral zone 

8  = dripping heater 

9  = button-operated load 1 

10 = button-operated load 2 

11 = alarm 

12 = on/stand-by 

99 

 

 

 

 

 

 

 

 

 

 

 

 

u3c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay K3 configuration 

 

 

 

 

 

 

 

 

 

 

 

 

0  = compressor 

1  = evaporator fan 

2  = condenser fan 

3  = defrost 

4  = cabinet light 

5  = demisting 

6  = door heaters 

7  = heater for neutral zone 

8  = dripping heater 

9  = button-operated load 1 

10 = button-operated load 2 

11 = alarm 

12 = on/stand-by 

100 

 

 

 

 

 

 

 

 

 

 

 

 

u4c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay K4 configuration 

 

 

 

 

 

 

 

 

 

 

 

 

0  = compressor 

1  = evaporator fan 

2  = condenser fan 

3  = defrost 

4  = cabinet light 

5  = demisting 

6  = door heaters 

7  = heater for neutral zone 

8  = dripping heater 

9  = button-operated load 1 

10 = button-operated load 2 

11 = alarm 

12 = on/stand-by 

101 

 

u2 

 

 

enable  cabinet  light  and  button-

operated load in stand-by 

0  = no 

1  = yes 

manual 

102 

 

u4 

 

 

enable  alarm  output  off  silencing 

the buzzer 

0  = no 

1  = yes 

 

103 

 

u5 

 

-1.0 

 

threshold for door heaters on 

 

-99... 99 °C/°F 

differential = 2 °C/4 °F 

104 

u6 

demisting on duration 

1... 120 min 

105 

 

 

u7 

 

 

-5.0 

 

 

neutral 

zone 

threshold 

for 

heating (relative to setpoint) 

 

-99... 99 °C/°F 

differential = 2 °C/4 °F 

se u7 

106 

u9 

enable alarm buzzer 

0  = no 

1  = yes 

 

N. 

PAR. 

DEF.  REAL TIME CLOCK 

MIN... MAX. 

107 

 

Hr0 

 

 

enable 

clock 

(default 

in 

EVJ254N7) 

0  = no 

1  = yes 

 

 

N. 

PAR. 

DEF.  ENERGY SAVING (if r5 = 0) 

MIN... MAX. 

108  HE2 

energy saving maximum duration  0... 999 min 

 

N. 

 

PAR. 

 

DEF. 

 

REAL  TIME  ENERGY  SAVING  (if 

r5 = 0) 

MIN... MAX. 

 

109  H01 

energy saving time 

0... 23 h 

110  H02 

energy saving maximum duration  0... 24 h 

 

N. 

PAR. 

DEF.  REAL TIME DEFROST (if d8 = 4) 

MIN... MAX. 

111  Hd1 

h- 

1st daily defrost time 

h- = disabled 

112  Hd2 

h- 

2nd daily defrost time 

h- = disabled 

113  Hd3 

h- 

3rd daily defrost time 

h- = disabled 

114  Hd4 

h- 

4th daily defrost time 

h- = disabled 

115  Hd5 

h- 

5th daily defrost time 

h- = disabled 

116  Hd6 

h- 

6th daily defrost time 

h- = disabled 

 

N. 

 

PAR. 

 

DEF. 

 

DATA-LOGGING  (not  available  in 

EVJ254N7)

 

MIN... MAX. 

 

117 

 

Sd0 

 

30 

 

SD card writing interval in HACCP 

mode 

1... 30 min 

 

118 

 

Sd1 

 

 

SD  card  writing  interval  in 

service mode 

1... 30 min 

 

119  Sd2 

60 

service mode duration 

1... 240 min 

120 

 

Sd3 

 

 

enable 

critical 

temperature 

recording 

0  = no 

1  = yes 

 

121 

 

Sd4 

 

 

enable 

cabinet 

temperature 

recording 

0  = no 

1  = yes 

 

122  Sd5 

decimal separator type 

0  = comma 

1  = point 

 

N. 

PAR. 

DEF.  SAFETIES 

MIN... MAX. 

123  POF 

enable ON/STAND-BY key 

0  = no 

1  = yes 

124 

 

 

Loc 

 

 

 

 

enable  keypad  lock  (default  0  in 

the models with open-frame user 

interface) 

0  = no 

1  = yes 

 

 

125 

 

 

Sen 

 

 

90 

 

 

sensitivity  capacitive  keyboard 

(available in the models installed 

from behind) 

60... 120 

60 = very sensitive 

 

126  PAS 

-19 

password 

-99... 999 

127  PA1 

426 

level 1 password 

-99... 999 

128  PA2 

824 

level 2 password 

-99... 999 

 

 

N. 

PAR. 

DEF.  DATA-LOGGING EVLINK 

MIN... MAX. 

129 

rE0 

60 

data-logger sampling interval 

0... 240 min 

130 

 

 

 

 

rE1 

 

 

 

 

 

 

 

 

recorded temperature 

 

 

 

 

0  = none 

1  = cabinet 

2  = evaporator 

3  = auxiliary 

4  = cabinet and evaporator 

5  = all 

 

N. 

PAR. 

DEF.  MODBUS 

MIN... MAX. 

131 

LA 

247 

MODBUS address 

1... 247 

132 

 

 

 

Lb 

 

 

 

 

 

 

MODBUS baud rate 

 

 

 

0  = 2,400 baud 

1  = 4,800 baud 

2  = 9,600 baud 

3  = 19,200 baud 

133 

 

LP 

 

 

parity 

 

0  = none 

1  = odd 

2  = even 

 

N. 

PAR. 

DEF.  BLUETOOTH 

MIN... MAX. 

131

bLE 

enable Bluetooth 

0  = no 

1  = yes 

 

ALARMS

 

 

COD.

 

DESCRIPTION

 

RESET

 

TO CORRECT

 

Pr1 

cabinet probe alarm 

automatic

 

-  check P0

 

Pr2

 

evaporator probe alarm 

automatic

 

-  check probe integrity

 

Pr3 

auxiliary probe alarm 

automatic

 

-  check electrical connection

 

rtc 

clock alarm 

manual 

set date, time and day of the week

 

AL 

low temperature alarm 

automatic

 

check A0, A1 and A2

 

AH 

high temperature alarm 

automatic

 

check A4 and A5

 

id 

open door alarm 

automatic

 

check i0 and i1

 

PF 

 

power failure alarm 

 

manual 

 

-  touch a key 

-  check electrical connection

 

COH 

high condensation warning 

automatic 

check C6 

CSd 

 

high condensation alarm 

 

manual 

 

-  switch the device off and on 

-  check C7 

iA 

multi-purpose input alarm 

automatic 

check i5 and i6 

iSd 

 

high pressure alarm 

 

manual 

 

-  switch the device off and on 

-  check i5, i6, i8, i9

 

LP 

 

low pressure alarm 

 

automatic 

 

check i5 and i6 

 

C1t 

 

compressor  thermal  switch 

alarm

 

automatic 

 

check i5 and i6 

 

dFd 

 

defrost timeout alarm 

 

manual 

 

-  touch a key 

-  check d2, d3 and d11

 

FUL 

 

SD card full alarm 

 

manual 

 

free  up  space  on  the  SD  card  or 

replace it

 

Sd 

No SD card inserted alarm

 

manual 

insert the SD card or replace it 

 

10 

TECHNICAL SPECIFICATIONS

 

 

Purpose of the control device

 

Function controller

 

Construction of the control device

 

Built-in electronic device

 

Container 

Models in plastic container

 

Black, self-extinguishing 

 

 

Open-frame models

 

Open-frame board

 

Category of heat and fire resistance

 

D

 

Measurements 

 

Models in plastic container 

 

111.4  x  76.4  x  48.0  mm 

(4 3/8 x 3 x 1 15/16 in) 

 

Open-frame models 

 

101.0  x  67.0  x  47.0  mm 

(4 x 2 5/8 x 1 7/8 in)

 

Mounting  methods  for  the 

control device 

 

 

 

 

 

 

Models in plastic container 

 

 

 

 

 

 

 

according  to  the  model,  front 

installation  on  a  plastic  or 

metal  panel  (with  elastic 

holding  flaps)  or  installed 

from  behind  a  glass  or 

methacrylate 

panel 

(with 

biadhesive)  customizing  the 

keys on the front of the unit

 

 

Open-frame models 

 

 

 

To  be  installed  from  behind, 

with 

threaded 

studs 

and 

membrane 

keypad 

(not 

provided)

 

Degree 

of 

protection 

provided by the covering 

 

 

 

Models in plastic container 

 

 

 

IP65 (front), on condition the 

device  is  fitted  to  a  metal 

panel  with  thickness  0.8  mm 

(1/32 in) 

Open-frame models

 

IP00

 

Connection method

 

 

 

 

Fixed  screw  terminal  blocks  for  wires up  to  2.5  mm²  (removable  screw  terminal  blocks  for 

wires up to 2,5 mm² by request)

 

Pico-Blade connector

 

Micro-MaTch connector

 

Maximum permitted length for connection cables

 

Power supply: 10 m (32.8 ft)

 

Analogue inputs: 10 m (32.8 ft)

 

Digital inputs: 10 m (32.8 ft) 

Analogue outputs: 3 m (9.84 ft) 

Digital outputs: 10 m (32.8 ft) 

Operating temperature

 

From -5 to 55 °C (from 23 to 131 °F)

 

Storage temperature

 

From -25 to 70 °C (from -13 to 158 °F)

 

Operating humidity 

 

Relative  humidity  without  condensate  from 

10 to 90%

 

Pollution status of the control device

 

Conformity 

 

 

 

RoHS 2011/65/CE 

 

WEEE 2012/19/EU 

 

REACH 

(EC) 

Regulation 

1907/2006

 

EMC 2014/30/UE 

LVD 2014/35/UE 

Power supply 

 

230  VAC  (+10%  -15%),  50/60  Hz  (±3  Hz), 

max. 6 VA insulated 

Earthing methods for the control device

 

None 

Rated impulse-withstand voltage

 

2.5 KV

 

Over-voltage category

 

II

 

Software class and structure

 

A

 

Clock 

 

Incorporated secondary lithium battery

 

(clock 

not available in EVJ254N7)

 

Clock drift

 

≤ 60 s/month at 25 °C (77 °F)

 

Clock  battery  autonomy  in  the  absence  of  a 

power supply

 

> 24 h at 25 °C (77 °F) 

 

Clock battery charging time 

 

24  h  (the  battery  is  charged  by  the  power 

supply of the device)

 

Analogue inputs 

 

2  for  PTC  or  NTC  probes  (cabinet  probe  and 

evaporator probe)

 

PTC probes

 

Sensor type

 

KTY 81-121 (990 

 @ 25 °C, 77 °F) 

 

Measurement field

 

From -50 to 150 °C (from -58 to 302 °F)

 

 

Resolution

 

0.1 °C (1 °F)

 

NTC probes

 

Sensor type

 

ß3435 (10 K

 @ 25 °C, 77 °F) 

 

Measurement field

 

From -40 to 105 °C (from -40 to 221 °F)

 

 

Resolution

 

0.1 °C (1 °F)

 

Digital inputs

 

1 dry contact (door switch)

 

Dry contact

 

Contact type

 

5 VDC, 1.5 mA 

 

 

Power supply

 

None

 

 

 

Protection

 

None

 

Other inputs 

 

Input  configurable  for  analogue  input  (auxiliary  probe)  or 

digital input (multi-purpose input) 

Analog outputs 

1 for PWM signal (compressor inverter) 

PWM signal 

Output 

9.5... 19 VDC, 10 mA 

 

Frequency 

0... 150 Hz 

 

Protection 

None 

Digital outputs 

4 with electro-mechanical relay

 

Relay K1

 

SPST, 16 A res. @ 250 VAC

 

Relay K2

 

SPDT, 8 A res. @ 250 VAC

 

Relay K3

 

SPST, 8 A res. @ 250 VAC

 

Relay K4

 

SPST, 5 A res. @ 250 VAC

 

The device guarantees double insulation between each digital output connector and the rest 

of the components of the device

 

Type 1 or Type 2 Actions

 

Type 1

 

Additional  features  of  Type  1  or  Type  2 

actions

 

 

Displays

 

Custom display, 3 digit, with function icons

 

Alarm buzzer

 

Incorporated

 

Incorporated sensors: 

 

Bluetooth 

Low 

Energy 

(available 

in 

EVJ254N7VXXRXV). 

Communications ports

 

1 TTL MODBUS slave port for EVconnect APP 

or BMS 

1  port  for  SD  card  data-logger  module 

EVBD05 (not available in EVJ254N7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 