EVCO S.p.A. | EVJ254 | Instruction sheet ver. 1.0 | Code 104J254I103 | Page 2 of 4 | PT 13/18 

 

rhH

 

high humidity function (evaporator fan on)

 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

5.4 

View/delete HACCP alarm information (not available in EVJ254N7) 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

LS 

view HACCP alarm information

 

 

rLS

 

delete HACCP alarm information

 

3. 

 

Touch the SET key.

 

4. 

 

Touch  the  UP  or  DOWN  key  to  select  an  alarm  code  (to  select 

label “LS”) or to set “149” (to select label “rLS”).

 

 

COD.

 

DESCRIPTION

 

 

AL 

low temperature alarm

 

 

AH

 

high temperature alarm

 

 

id

 

open door alarm (if i4 = 1)

 

 

PF 

 

power  failure  alarm  (available  in  EVJ254N7VXXRXV  or  in  EVJ254N7  with 

interface EVIF25TBX connected)

 

5. 

 

Touch the SET key.

 

6. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure. 

 

Example of alarm information (e.g. a high temperature alarm). 

 

 

8.0 

 

 

critical  value  (calculated  cabinet/product  temperature) 

was 8.0 °C/°F

 

 

 

Sta 

 

(available  in  EVJ254N7VXXRXV  or  in  EVJ254N7  with  interface 

EVIF25TBX connected) 

 

 

 

y15

 

alarm signalled in 2015

 

 

 

 

n03

 

alarm signalled in March

 

 

 

 

d26

 

alarm signalled on 26 March 2015

 

 

 

 

h16

 

alarm signalled at 16:00

 

 

 

 

n30

 

alarm signalled at 16:30

 

 

 

dur

 

 

 

 

 

 

h01

 

alarm lasted 1h

 

 

 

 

n15

 

alarm lasted 1h 15min

 

 

 

5.5 

View/delete compressor functioning hours 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

CH1

 

view compressor functioning hundreds of hours

 

 

rCH 

delete compressor functioning hours

 

3. 

 

Touch the SET key.

 

4. 

 

Touch the UP or DOWN key to set “149” (to select rCH).

 

5. 

 

Touch the SET key.

 

6. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

5.6 

View the temperature detected by the probes 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

Pb1 

cabinet temperature (if P4 = 0, 1 or 2)

 

 

inlet air temperature (if P4 = 3)

 

 

Pb2

 

evaporator temperature (if P3 = 1 or 2)

 

 

Pb3

 

auxiliary temperature (if P4 = 1, 2 or 3)

 

 

Pb4 

calculated product temperature (CPT; if P4 = 3)

 

3. 

 

Touch the SET key.

 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

5.4 

View the percentage of the supplied PWM signal 

Assicurarsi che la tastiera non sia bloccata. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select “PoU”. 

3. 

 

Touch the SET key. 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

 

DATA-LOGGER MODULE on SD CARD (not available in EVJ254N7)

 

6.1 

Initial information 

The data-logger module makes it possible to write information about the device on an SD card 

(in CSV format ), in HACCP or service mode. 

Data-logger module configuration parameters. 

PAR.

 

DEF.

 

PARAMETER

 

MIN... MAX. 

Sd0 

 

30 

 

SD  card  writing  interval  in  HACCP 

mode 

1... 30 min 

 

Sd1 

 

 

SD  card  writing  interval  in  service 

mode 

1... 30 min 

 

Sd2 

60 

service mode duration 

1... 240 min 

Sd3 

enable critical temperature recording 

0  = no 

1  = yes 

Sd4 

enable cabinet temperature recording 

0  = no 

1  = yes 

Sd5 

decimal separator type 

0  = comma 

1  = point

 

 

6.2 

Writing in HACCP mode 

Writing in HACCP mode is always activated, it generates a daily file and a monthly file. 

Information written in HACCP mode. 

cabinet temperature (if Sd4 = 1, default “no”) 

critical temperature (if Sd3 = 1, default “no”) 

device switched on/off  

defrost activated/completed 

energy saving activated/deactivated 

alarm activated/restored 

power supply restored 

The date and time is written for each piece of information. 

 

6.3 

Writing in service mode 

Writing in service mode must be manually activated. 

Information written in service mode. 

temperature detected by all probes 

enable/disable probes 

device switched on/off  

functions on/off  

defrost activated/completed 

energy saving activated/deactivated 

alarm activated/restored 

power supply restored 

The date and time is written for each piece of information. 

 

6.4 

Activate/deactivate writing in service mode  

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select the label  “SEr”.

 

3. 

 

Touch the SET key.

 

4. 

 

Touch  the  UP  or  DOWN  key  within  15s  to  set  “1”  (activate 

writing) or “0” (deactivate writing).

 

5. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

6.5 

File names 

Example of a daily file name written in HACCP mode (e.g. the file “log001_2015_03_26.csv”). 

 

001 

the device address is 1 (parameter LA)

 

 

 

2015 

the file was written in 2015

 

 

 

03 

the file was written in March

 

 

 

26 

the file was written on 26 March 2015

 

 

 

Example of a monthly file name written in HACCP mode (e.g. the file “log001_2015_m03.csv”). 

 

001 

the device address is 1 (parameter LA)

 

 

 

2015 

the file was written in 2015

 

 

 

m03

 

the file was written in March 2015

 

 

 

Example of a file name written in service mode (e.g. the file “log001_2015_0001.csv”). 

 

001 

the device address is 1 (parameter LA)

 

 

 

2015 

the file was written in 2015

 

 

 

0001 

sequence number

 

 

 

6.6 

View data-logger module alarms 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select the label  “Err”.

 

3. 

 

Touch the SET key.

 

4. 

 

Touch the UP or DOWN key within 15s to see the alarm code.

 

 

 

LAB. 

DESCRIPTION

 

 

FUL

 

no space left on SD card alarm

 

 

Sd

 

SD card not inserted or not recognised alarm

 

5. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

SETTINGS

 

7.1 

Setting configuration parameters 

1. 

 

Touch the SET key for 4s: the display will show the label “PA”.

 

2. 

 

Touch the SET key.

 

3. 

 

Touch  the  UP  or    DOWN  key  within  15s  to  set  the  PAS  value 

(default “-19”).

 

4. 

 

Touch  the  SET key  (or  do  not  operate  for  15s):  the  display  will 

show the label “SP”.

 

5. 

 

Touch the UP or DOWN key to select a parameter.

 

6. 

 

Touch the SET key.

 

7. 

 

Touch the UP or DOWN key within 15s to set the value.

 

8. 

 

Touch the SET key (or do not operate for 15s).

 

9. 

 

Touch the SET key for 4s (or do not operate for 60s) to exit the 

procedure.

 

 

7.2 

Set  the  date,  time  and  day  of  the  week  (available  in  EVJ254N7VXXRXV  or  in 

EVJ254N7 with interface EVIF25TBX connected) 

 

 

N.B. 

-  If the device is connected to the interface EVIF25TBX, do not disconnect the device 

from  the  mains  within  two  minutes  since  the  setting  of  the  time  and  day  of  the 

week. 

-  If the device communicates with the APP EVconnect, the date, time and day of the 

week will automatically be set by the smartphone or tablet. 

 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select the label  “rtc”.

 

3. 

 

Touch  the  SET  key:  the  display  will  show  the  label  “y”  followed 

by the last two figures of the year.

 

4. 

 

Touch the UP or DOWN key within 15s to set the year.

 

5. 

Repeat actions 3 and 4 to set the next labels.

 

 

LAB.

 

MEANING OF THE NUMBERS FOLLOWING THE LABEL

 

 

month (01… 12)

 

 

day (01… 31)

 

 

time (00… 23)

 

 

n

 

minutes (00… 59)

 

6. 

 

Touch the SET key: the display will show the label for the day of 

the week.

 

7. 

 

Touch  the  UP  or  DOWN  key  within  15s  to  set  the  day  of  the 

week.

 

 

LAB.

 

DESCRIPTION

 

 

Mon 

Monday

 

 

tuE 

Tuesday

 

 

UEd 

Wednesday

 

 

thu

 

Thursday

 

 

Fri 

Friday

 

 

Sat 

Saturday

 

 

Sun 

Sunday

 

8. 

 

Touch the SET key: the device will exit the procedure.

 

9. 

 

Touch the ON/STAND-BY key to exit the procedure beforehand.

 

 

7.3 

Reset the factory settings 

 

 

N.B. 

Check  that  the  factory  settings  are  appropriate;  see  the  section  CONFIGURATION 

PARAMETERS.

 

 

1. 

 

Touch the SET key for 4s: the display will show the label “PA”.

 

2. 

 

Touch the SET key.

 

3. 

 

Touch the UP or DOWN key within 15s to set “149”.

 

4. 

 

Touch  the  SET key  (or  do  not  operate  for  15s):  the  display  will 

show the label “dEF”.

 

5. 

 

Touch the SET key.

 

6. 

 

Touch the UP or DOWN key within 15s to set “1”.

 

7. 

 

Touch the SET key (or do not operate for 15s).

 

8. 

Interrupt the power supply to the device.

 

9. 

 

Touch  the  SET  key  for  2s  before  action  6  to  exit  the  procedure 

beforehand.

 

 

CONFIGURATION PARAMETERS

 

 

 

N. 

PAR. 

DEF.  SETPOINT 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

 

N. 

PAR. 

DEF.  ANALOGUE INPUTS 

MIN... MAX. 

 

CA1 

 

0.0 

 

cabinet probe offset 

 

-25... 25 °C/°F 

if P4 = 3, air in probe offset 

CA2 

0.0 

evaporator probe offset 

-25... 25 °C/°F 

CA3 

0.0 

auxiliary probe offset 

-25... 25 °C/°F 

P0 

probe type 

0  = PTC 

1  = NTC 

P1 

enable °C decimal point 

0  = no 

1  = yes 

 

P2 

 

 

temperature 

unit 

of 

measurement 

0  = °C 

1  = °F 

 

 

 

P3 

 

 

 

 

evaporator probe function 

 

 

0  = disabled 

1  = d fan 

2  = fan 

 

 

 

 

 

 

P4 

 

 

 

 

 

 

 

 

 

 

 

 

configurable input function 

 

 

 

 

 

 

0  = digital input 

1  = condenser probe 

2  = critical temperature probe 

3  = air out probe 

4  = evaporator 2 probe 

if P4 = 3, regulation temperature 

= product temperature (CPT) 

10 

 

 

 

 

P5 

 

 

 

 

 

 

 

 

value displayed 

 

 

 

 

0  = regulation temperature 

1  = setpoint 

2  = evaporator temperature 

3  = auxiliary temperature 

4  = air in temperature 

11 

 

 

 

P7 

 

 

 

50 

 

 

 

inlet  air  weight  for  calculated 

product temperature (CPT) 

 

 

0... 100 % 

CPT = {[(P7 x (inlet air T)] + 

[(100 - P7) x (outlet air T)] : 

100} 

12 

P8 

display refresh time 

0... 250 s : 10 

 

N.

 

PAR.

 

DEF.

 

REGULATION

 

MIN... MAX.

 

13 

r0 

2.0 

setpoint differential 

1... 15 °C/°F 

14 

r1 

-40 

minimum setpoint 

-99 °C/°F... r2 

15 

r2 

50.0  maximum setpoint 

r1... 199 °C/°F 

16 

r3 

enable setpoint block

 

0  = no 

1  = yes 

17 

r4 

0.0 

setpoint offset in energy saving 

0... 99 °C/°F 

18 

 

r5 

 

 

cooling or heating operation 

 

0  = cooling 

1  = heating 

19 

 

r6 

 

0.0 

 

setpoint 

offset 

in 

overcooling/overheating 

0... 99 °C/°F 

 

20 

r7 

overcooling/overheating duration 

0... 240 min 

21 

 

r12 

 

 

position of the r0 differential 

 

0  = asymmetric 

1  = symmetric 

22 

 

r13 

 

25.0 

 

proportional  band  (relative  to 

setpoint) 

0... 99 °C/°F 

se r13 

23 

r14 

10 

integral action time 

0... 99 min 

24 

 

 

 

 

 

r15 

 

 

 

 

 

 

 

 

 

 

compressor type 

 

 

 

 

 

1  = Embraco VEM 

2  = Embraco VEG 

3  = Embraco VNEK e VNEU 

4  = Secop  VNL  50...  150  Hz 

    (40 Hz in off) 

5  = Secop 33... 133 Hz 

 

N. 

PAR. 

DEF.  COMPRESSOR 

MIN... MAX. 

25 

 

CP0 

 

 

time  compressor  at  85  Hz  after 

power-on 

0... 100 s x 10 

 

26 

 

C0 

 

 

compressor 

on 

delay 

after 

power-on 

0... 240 min 

 

27 

 

C1 

 

 

delay  between  2  compressor 

switch-ons

 

0... 240 min 

 

28 

C2 

compressor off minimum time 

0... 240 min 

29 

C3 

compressor on minimum time 

0... 240 s 

30 

 

C4 

 

10 

 

compressor 

off 

time 

during 

cabinet probe alarm 

0... 240 min 

 

31 

 

C5 

 

10 

 

compressor 

on 

time 

during 

cabinet probe alarm 

0... 240 min 

 

32 

 

C6 

 

80.0 

 

threshold  for  high  condensation 

warning 

0... 199 °C/°F 

differential = 2 °C/4 °F 

33 

 

C7 

 

90.0 

 

threshold  for  high  condensation 

alarm 

0... 199 °C/°F 

 

34 

C8 

high condensation alarm delay 

0... 15 min 

35 

 

 

 

C9 

 

 

 

 

 

 

consecutive 

time 

cabinet 

temperature in proportional band 

for  compressor  at  maximum 

speed 

0... 99 h 

0  = disabled 

until  cabinet  temperature  < 

setpoint 

36 

 

C10 

 

 

compressor hours for service 

 

0... 999 h x 100 

0  = disabled 

 

N. 

PAR. 

DEF.  DEFROST (if r5 = 0) 

MIN... MAX. 

37 

 

 

d0 

 

 

 

 

automatic defrost interval 

 

 

0... 99 h 

0  = only manual 

if d8 = 3, maximum interval 

38 

 

 

d1 

 

 

 

 

defrost type 

 

 

0  = electric 

1  = hot gas 

2  = compressor stopped 

39 

d2 

2.0 

threshold for defrost end 

-99... 99 °C/°F 

40 

 

d3 

 

30 

 

defrost duration 

 

0... 99 min 

se P3 = 1, maximum duration 

41 

d4 

enable defrost at power-on 

0  = no 

1  = yes 

42 

d5 

defrost dealy after power-on 

0... 99 min 

43 

 

 

d6 

 

 

 

 

value displayed during defrost 

 

 

0  = regulation temperature 

1  = display locked 

2  = dEF label 

44 

d7 

dripping time 

0... 15 min 

45 

 

 

 

 

 

 

d8 

 

 

 

 

 

 

 

 

 

 

 

 

defrost interval counting mode 

 

 

 

 

 

 

0  = device on hours 

1  = compressor on hours 

2  = hours 

evaporator 

temperature < d9 

3  = adaptive  (if  P4  =  4, 

device on hours) 

4  = real time 

46 

 

 

d9 

 

 

0.0 

 

 

evaporation 

threshold 

for 

automatic 

defrost 

interval 

counting 

-99... 99 °C/°F 

 

 

47 

d11 

enable defrost timeout alarm 

0  = no 

1  = yes 

48 

 

 

d15 

 

 

 

 

compressor  on  consecutive  time 

for hot gas defrost 

 

-20... 99 min 

if  negative  values,  duration 

dripping heater on 

49 

 

d16 

 

 

pre-dripping  time  for  hot  gas 

defrost 

0... 99 min 

 

50 

 

 

 

d18 

 

 

 

40 

 

 

 

adaptive defrost interval 

 

 

 

0... 999 min 

if  compressor  on  +  evapora-

tor temperature < d22 

0  = only manual 

51 

 

 

d19 

 

 

3.0 

 

 

threshold  for  adaptive  defrost 

(relative  to  optimal  evaporation 

temperature) 

0... 40 °C/°F 

optimal 

evaporation 

temperature - d19 

52 

 

d20 

 

180 

 

compressor  on  consecutive  time 

for defrost 

0... 999 min 

0  = disabled 

53 

 

 

 

d21 

 

 

 

200 

 

 

 

compressor  on  consecutive  time 

for  defrost  after  power-on  and 

overcooling  

 

0... 500 min 

if  (regulation  temperature  - 

setpoint) > 10°C/20 °F 

0  = disabled 

54 

 

 

 

d22 

 

 

 

-2.0 

 

 

 

evaporation 

threshold 

for 

adaptive defrost interval counting 

(relative  to  optimal  evaporation 

temperature) 

-10... 10 °C/°F 

optimal 

evaporation 

tempe d22 

 