(3) the parameter only has effect after a power cut that occurs when the instrument is on
(4) the time established with the parameter is counted also when the instrument is off
(5) if parameter C1 is set at 0, the delay from the conclusion of the cabinet probe error will be 2 min
(6) the parameter differential is 2.0 

°

C/4 

°

F

(7) on instrument switch-on, the temperature of the condenser is already above that established with parameter C7, parameter C8 will have no effect
(8) the instrument memorises the defrosting interval count every 30 min. The modification of parameter d0 has effect from the conclusion of the previous defrosting interval or from the activation of defrosting in manual

mode

(9) the display restores normal functioning when, on conclusion of evaporator fan standstill, the cabinet temperature drops below that which has blocked the display (or if a temperature alarm occurs)
(10) if parameter P3 is set at 0 or 2, the instrument will function as if parameter d8 is set at 0
(11) if, on activation of defrosting, the switch-on duration of the compressor is less than the time established with parameter d15, the compressor will remain on for the fraction of time required to complete it
(12) if parameter P3 is set at 0, the instrument will function as if parameter A0 is set at 0 but will not memorise the alarm
(13) during defrosting, dripping and evaporator fan standstill, the temperature alarms are not present as long as these have occurred after activation of defrosting
(14) during the activation of the door micro switch input, the maximum temperature alarm is absent on the condition that these occur after activation of the input
(15) the alarm is always signalled when the power supply is restored
(16) if parameter P3 is set at 0, the instrument will function as if parameter F0 is set at 2
(17) the parameter is also modified by operating with the procedure given in paragraph 4.8.1
(18) if parameter P4 is set at 0, the condenser fan will function in parallel to the compressor
(19) the compressor is switched-off after 10 s from activation of the input. If the input is activated during defrosting or standstill of the evaporator fan, the activation will not have any effect on the compressor
(20) the instrument memorises the alarm on expiry of the time established with parameter i2. If parameter i2 is set at -1, the instrument does not memorise the alarm
(21) make sure that the time established with parameter i7 is lower than that established with parameter i9
(22) to prevent damage to the utility connected, modify the parameter when the instrument is off
(23) if parameter u2 is set at 0, instrument switch-off will cause the cabinet light and/or auxiliary output to switch off (on successive switch-on of the instrument, the utility will remain off); if the parameter u2 is set at 1,

instrument switch-off will not cause the cabinet light and/or auxiliary output to switch off (on successive switch-on of the instrument, the utility will remain on).

13

ELECTRIC CONNECTION

13.1

Preliminary considerations

With reference to the wiring diagram:
• the utility managed by the fourth output will depend on parameter u1
• the utility managed by the fifth output will depend on parameter u11
• the serial is the port for communication with the Parameters Manager set-up software system or to the monitoring and supervision system of RICS plants (through a serial interface, via TTL, with MODBUS communication

protocol) or with the EVKEY programming key. The port must not be used simultaneously for three purposes.

13.2

Electric connection

13.3

Recommendations for the electric connection

• do not operate on the terminal boards using electric or pneumatic screwdrivers
• if the instrument has been taken from a old place to a hot one, the humidity could condense inside. Wait about one hour before applying power
• make sure that the power supply voltage, frequency and operational electric power correspond to those of the local power supply
• disconnect the power supply before performing any type of maintenance
• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the Evco sales network.

Summary of Contents for EVF215

Page 1: ...module must be at a distance such as not to compromise the safety distances make sure the display is perfectly adherent to the methacrylate in compliance with Safety Standards the protection against any contact with the electric parts must be ensured via correct installation of the instrument All parts that ensure protection must be fixed in a way such that they cannot be removed without the aid o...

Page 2: ...nctioning hours These operations cause the Loc label to be displayed for 1 s To unlock the keyboard press and hold the and key for 1 s the display will show UnL for 1 s 4 14 Silencing the buzzer make sure no procedure is in progress press a key the first time the key is pressed does not cause the associated effect If parameter u1 and or parameter u11 is set at 3 and parameter u4 is set at 1 pressi...

Page 3: ...alarm output will be activated only if parameter u1 and or parameter u11 is set at 3 iSd Pressure switch alarm Solutions check the causes that brought about the activation of the input see parameters i5 i6 i7 i8 and i9 switch the instrument off and back on again or cut the power supply off Main consequences the regulators will be switched off the alarm output will be activated only if parameter u1...

Page 4: ...ck the data related in the labels Main consequences the control module will keep working correctly ErL Error of communication user interface control module Solutions check the connection user interface control module Main consequences the control module will keep working correctly When the cause of the alarm disappears the instrument restores normal functioning except for the clock error rtc code ...

Page 5: ...ance request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECTRIC during defrosting the compressor will remain off and the defrosting output will be activated the evaporator fan activity will depend on parameter F2 1 WITH HOT GAS during defrosting the compressor...

Page 6: ...tioning 0 off 1 on se also F13 F14 and i10 2 parallel to the compressor se also F9 F13 F14 and i10 3 depending on F1 16 4 off if the compressor is off depending on F1 if the compressor is on see also F9 16 5 depending on F6 see also F9 evaporator temperature over which the evaporator fan is switched off sonly if F0 3 or 4 see also F8 activity of the evaporator fan during defrosting and dripping 0 ...

Page 7: ...ue from those used for the calculation of the relative average for the activation of defrosting only if d8 3 see also d17 number of door micro switch input activations such to cause the activation of defrosting 0 defrosting will never be activated due to the effect of door micro switch input activation minimum duration of door micro switch input activations such to cause the activation of defrosti...

Page 8: ... always signalled when the power supply is restored 16 if parameter P3 is set at 0 the instrument will function as if parameter F0 is set at 2 17 the parameter is also modified by operating with the procedure given in paragraph 4 8 1 18 if parameter P4 is set at 0 the condenser fan will function in parallel to the compressor 19 the compressor is switched off after 10 s from activation of the input...

Reviews: