EVCO S.p.A.
EVDRIVE06 | User manual ver. 1.0 | Code 144EPD4I114
Page 49 of 78
P1YM
1652
RW
P1Ym
300.00 barG/barA
1.00
Manufact.
Y max value
P1Ym 1653
RW
-
300.00
P1YM
barG/barA
0.00
Manufact.
Y min value
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI2
Piu2
1654
RW
0
2
- - - -
0
Manufact.
analog input AI2 function
0 = not used
1 = suction
temperature
backup
probe
2 = suction
pressure
backup
probe
Pia2
1655
RW
1
30
- - - -
20
Installer
analog input AI2 probe type
(used if Piu2 = 1 or 2)
1 = NTC probe
6 = Pt 1000 probe
10 = 4÷20 mA transducer
(0÷10 Barg)
11 = 4÷20 mA transducer
(0÷16 Barg)
12 = 4÷20 mA transducer
(0÷30 Barg)
13 = 4÷20 mA transducer
(0÷50 Barg)
20 = 0÷5 V ratiometric transducer
(0÷7 Barg)
21 = 0÷5 V ratiometric transducer
(0÷25 Barg)
22 = 0÷5 V ratiometric transducer
(0÷60 Barg)
30 = scaling
AI2T
518
RW
2
7
- - - -
5
User
AI1 type (used if Piu2 = 0)
2 = NTC
3 = 0-20 mA
4 = 4-20 mA
5 = 0-5 V
6 = reserved
7 = Pt 1000
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI2
scaling
P2Xty 1656
RW
0
2
- - - -
0
Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
2 = 0-5 V
P2XM
1657
RW
P2Xm
0:20.00
- - - -
20.00
Manufact.
X max value